摘要
介绍了一起1000MW超超临界机组因处理除氧器水位变送器接头漏水,引起除氧器虚假水位信号,导致除氧器及辅汽联箱进汽切除的异常事件经过,分析了该起异常事件的原因,制定了相应的防范措施,为防范同类故障提供参考。
This paper introduces an abnormal event occurred in an 1 000 MW ultra supercritical fossil-fired unit that the treatment of water leakage in deaerator level transmitter connector causes deaerator false water level signal and finally results in the removal of inlet steam of deaerator and auxiliary steam header. This paper analyzes the causes of the abnormal event and puts forward corresponding preventive measures, which can serve as a reference for preventing similar faults.
作者
王彦领
张振宇
蒙在朗
王浩
WANG Yanling;ZHANG Zhenyu;MENG Zailang;WANG Hao(Pingdingshan Power Generation Company of State Power Investment Henan Power Generation Co.,Ltd.,Pingdingshan467312,Henan Province,China;State Power Investment Henan Power Generation Co.,Ltd.,Zhengzhou 450001,Henan Province,China)
出处
《电力安全技术》
2019年第5期27-29,共3页
Electric Safety Technology
关键词
除氧器
水位变送器
平衡容器
虚假水位
deaerator
water level transmitter
equilibrium vessel
false water level