摘要
比较了新风深度冷却除湿系统与一次回风再热系统的空气热湿处理过程。以某手术室为例,计算分析了2种空气热湿处理方案的适用性。结果表明,由于存在新风处理临界点,洁净手术室采用新风深度冷却除湿系统的总负荷并不总是小于一次回风再热系统。
Compares the air handling process of outdoor air depth cooling dehumidification system and primary return air reheating system. Taking an operating room as an example, calculates and analyses the applicability of two air handling process projects. The results show that the total load of the outdoor air depth cooling dehumidification system is not always less than that of the primary return air reheating system in clean operating room because of the critical point of outdoor air treatment.
作者
姚东文
Yao Dongwen(China Rehabilitation Research Center,Beijing, China)
出处
《暖通空调》
2019年第6期54-57,共4页
Heating Ventilating & Air Conditioning
关键词
新风
深度冷却除湿
洁净手术室
热湿处理过程
节能
适用性
新风处理临界点
outdoor air
depth cooling dehumidification
clean operating room
heat and moisture handling process
energy saving
applicability
critical point of outdoor air treatment