摘要
介绍了一起断路器合闸不到位故障,通过现场检查、尺寸测量、故障模拟、金属检测,明确故障原因为提升杆与绝缘拉杆连接销轴端部的弹性锁片未安装或安装工艺不良,最终导致销轴产生移位并与下支撑座内壁产生摩擦,使得合闸阻力增大,导致断路器合闸不到位。并根据故障具体原因,提出了相应的排查措施。
A circuit breaker poor closing failureis analyzed.Through field inspection,size measurement,fault simulation and metal detection,it is found that the absence or poor installation of the locking piece at the end of the joint pin of hoisting rod and insulation rod causespin displacement and friction with the inner wall of the lower support,which increases the closing resistance and hence results in the inadequate closing failure of the circuit breaker.Accordingly,corresponding countermeasures are put forward.
作者
陈宇民
赵现平
彭晶
王科
马仪
谭向宇
张恭源
孙傲阳
许宏伟
白双全
朱云武
CHEN Yumin;ZHAO Xianping;PENG Jing;WANG Ke;MA Yi;TAN Xiangyu;ZHANG Gongyuan;SUN Aoyang;XU Hongwei;BAI Shuangquan;ZHU Yunwu(Yunnan Power Grid Co.,Ltd.,Kunming 650011,China;Electric Power Research Institute,Yunnan Power Grid Co.,Ltd.,Kunming 650217,China;Chuxiong Power Supply Bureau,Yunnan Power Grid Co.,Ltd.,Yunnan Chuxiong 675000,China;Kunming Power Supply Bureau,Yunnan Power Grid Co.,Ltd.,Kunming 650011,China)
出处
《高压电器》
CAS
CSCD
北大核心
2019年第6期247-252,共6页
High Voltage Apparatus
关键词
断路器
销轴
缺陷
合闸不到位
故障分析
circuit breaker
pin
defect
inadequate closing
failure analysis