摘要 针对一起110kV GIS母线TV分支气室局放异常缺陷,开展了超声波局部放电带电检测。结合局放信号源超声波精确定位,经定性分析,综合判断该气室内部存在连接件松动的可能。考虑设备长期运行,内部连接件松动会产生放电和故障隐患,建议结合气室内部结构图纸进行停电解体检查。 In this paper,considering an abnormal defect of partial discharge in 110 kV GIS bus air chamber,the ultrasonic partial discharge(PD)live detection is carried out.Based on the precise location of partial discharge signal source and qualitative analysis,the possibility of loosening connectors in the gas chamber is judged comprehensively.Considering the long-term operation of the equipment,it is suggested that the outage electrolytic examination should be carried out in combination with the internal structure drawings of the gas chamber.
作者 顾宇宏 曹斌 侯宇嘉 刘博 GU Yuhong;CAO Bin;HOU Yujia;LIU Bo(Inner Mongolia Power Research Institute,Hohhot 010020,China;PDStars Electric Co.,Ltd.,Shanghai 201100,China)
出处 《内蒙古电力技术》 2019年第3期71-73,共3页 Inner Mongolia Electric Power
关键词 GIS 局部放电 带电检测 精确定位 GIS partial discharge electrification detection accurate location
  • 相关文献

参考文献2

二级参考文献36

  • 1段一雄.GIS局部放电试验研究情报综述[J].云南电力技术,1995,23(2):45-48. 被引量:4
  • 2吴广宁,马积勋,吴欣延,谢恒堃,陈志清,孙德琳.大型电机局部放电监测用宽频电流传感器及应用的研究[J].西安交通大学学报,1996,30(6):8-14. 被引量:14
  • 3江本邦夫 村濑洋.用表面电流传感器的GCB用便携式诊断装置的开发[J].电学论B,1998,118(6):666-666.
  • 4IEC-270标准..[S].,..
  • 5Dakin T W, Malinaric P J. A capacitive bridge method for measuring integrated corona-charge transfer and power loss per cycle. Trans AIEE PAS, 1960,79: 648~653.
  • 6Izeki N, Tatsuta F. Three types of partial discharges in electrical insulation. Conf. Record on IEEE Intern. Symp. in El. Ins., Montreal 1984: 327~331.
  • 7Boggs S A, Stone C. Fundamental limitations in the measurement of corona and partia discharge. IEEE Trans. on EI 1982, 17 (2): 143~150.
  • 8Dakin T W, Malinaric P J. A capacitive bridge method for measuring integrated corona-charge transfer and power loss per cycle. Trans AIEE PAS 1960, 79:648~653.
  • 9Izeki N, Tatsuta F. Three types of partial discharges in electrical insulation. Conf. Record on IEEE Intern. Symp. in El. Ins., Montreal, 1984: 327~331.
  • 10Lemke E. A new partial discharge measuring procedure based on the evaluation of the cumulative charge. Conf. on PD in Electrical Insulation Bangalore/ India ,1976:1~22.