摘要
本文基于可再生能源并网发电系统公共耦合点电压存在背景谐波,建立了并网逆变器的等效电路模型,解析了公共耦合点处电压背景谐波影响并网逆变器输出电流的机理,在控制环路中引入多谐振控制器改善了并网逆变器的输出电能质量,并给出了一种多谐振控制器参数设计的方法。最后,在仿真软件中搭建了可再生能源发电系统和配电网的模型,设定了电网背景谐波参数,分别进行了有无多谐振控制器控制策略的仿真实验,实验结果验证了本文采用的控制策略的正确性和可行性。
In this paper,the equivalent circuit model of grid-connected inverter is established with considering the background harmonics of common coupling point voltage in renewable generation system. The mechanism of the influence of voltage background harmonics at common coupling point on the output current of grid-connected inverter is analyzed. A multi-resonant controller is introduced into the control loop to improve the output power quality of grid-connected inverter. Parameter design method of multi-resonant controller is given. Finally,the model of renewable energy generation system and distribution network is built in the simulation software,and the background harmonic parameters are set. The simulation experiments of the control strategy with or without multi-resonant controller are carried out respectively. The correctness and feasibility of the control strategy used in this paper is verified by the experimental result.
作者
谢佳
孙韬
XIE Jia;SUN Tao(Skills Training Center of State Grid Chongqing Electric Power Company, Chongqing 400053, China;State Key Laboratory of Power Transmission Equipment & System Security and New Technology in Chongqing University, Chongqing 400044, China)
出处
《电力电容器与无功补偿》
北大核心
2019年第3期148-152,共5页
Power Capacitor & Reactive Power Compensation
关键词
电网谐波
并网逆变器
谐振控制器
grid harmonics
grid connected inverter
resonant controller