送风方式对热通道封闭数据中心热环境影响的模拟研究 被引量:14

Simulation Research on Effect of Air Supply Method on Thermal Environment of Hot Aisle Contained Data Center
下载PDF
导出
摘要 以实际项目的机房为例,利用数据中心专用模拟软件6SigmaRoom,研究热通道封闭数据中心的最佳送风方式,对比分析机架下送风和地板下送风情况下,满足ASHRAE2011温度标准的机柜数量、机房内边缘热点的IT设备数量、机柜数量及不同截面的温度、速度分布情况,并选取几个典型的热环境评价指标定量分析机房热环境。研究表明,由于地板下送风受送风静压箱和地板开孔率的影响较大,热通道封闭的数据中心宜与机架下送风方式相结合,充分利用冷量,达到节能的目的。 By taking the actual computer room as an example,the special simulation software 6SigmaRoom for data centers was used to study the optimal air supply method for the hot aisle contained data center,the number of cabinets satisfying the ASHRAE2011 temperature standard,the number of IT equipment and number of cabinets,temperature and velocity distribution of different cross-sections at hot spots on the edge of the equipment room were comparatively analyzed for the under-rack air supply and the under-floor air supply,and several typical thermal environment evaluation indicators were selected to quantitatively analyze the thermal environment of the computer room.The study shows that because the air supply under the floor is greatly affected by the static pressure box and the floor opening rate,the data center with contained hot aisle should be combined with the air supply method under the rack to fully utilize the cooling capacity to achieve the purpose of energy conservation.
作者 李婷婷 黄翔 耿志超 Li Tingting;Huang Xiang;Geng Zhichao(Xi'an Polytechnic University,Xi'an 710048,China)
机构地区 西安工程大学
出处 《流体机械》 CSCD 北大核心 2019年第6期62-67,共6页 Fluid Machinery
基金 “十三五”国家重点研发计划项目课题(2016YFC0700404) 西安工程大学研究生创新基金资助项目(chx201869)
关键词 送风方式 数据中心 热通道封闭 数值模拟 supply air method data center hot aisle containment numerical simulation
  • 相关文献

参考文献3

二级参考文献6

共引文献44

同被引文献134

引证文献14

二级引证文献67

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部