对冷水机组实际性能系数(COPd)进行检测,指出现场检测相关细节问题,并通过实际工程案例分析不同负荷下COPd的变化,认为冷水机组高效区范围为负荷率60%~80%,稳定区范围为负荷率80%以上。研究结果可供检测和施工相关方参考。
The actual performance of coefficient (COPd) for chiller is tested on-site, the corresponding details for on-site detection are pointed out. At the same time, the changes of COPd under different operation loads are analyzed through practical engineering cases .It is concluded that the range of high efficiency zone is between 60 % and 80 % of the operation load of chiller, and the range of stable zone is above 80%. It can be used as a reference for related parties of detection and construction.