期刊文献+

Experimental investigation on oil-gas separator of air-conditioning systems 被引量:1

原文传递
导出
摘要 The oil-return system plays an important role in the variable refrigerant flow (VRP) systems because it ensures the reliable operation of the VRF systems. The oil-gas separator is the most essential component of the oil- return system, and the separation efficiency of the separator directly influences the performance of the VRF systems. Therefore, in this paper, a test rig was built to measure the oil discharge ratio of the compressor and the separation efficiency of the oil-gas separator. A sound velocity transducer was used to measure the oil mass concentration instantaneously, because the sound velocity was changed with the mass ratio of oil to refrigerant. The separation efficiency of the separator could be obtained by comparing the mass fraction of oil to refrigerant before and after the separator was connected to the system.
出处 《Frontiers in Energy》 SCIE CSCD 2019年第2期411-416,共6页 能源前沿(英文版)
  • 相关文献

参考文献2

二级参考文献10

  • 1褚晓冬.螺杆压缩机油气分离器内部流场的数值模拟[J].通用机械,2006(1):86-89. 被引量:5
  • 2冯健美,畅云峰,屈宗长,姚建国.油气分离器内油滴运动轨迹的数值模拟[J].西安交通大学学报,2006,40(7):771-775. 被引量:16
  • 3孙秀君,孙海鸥,姜任秋.油气分离器内油滴轨迹的数值模拟[J].应用科技,2006,33(10):69-72. 被引量:16
  • 4Wei W J, Ding G L, Wang K J. Measurement and correlation of two-phase frictional performance of refrigerant-oil mixtures inside small tubes [J]. HVAC & R Research, 2007, 13 (2): 397-411.
  • 5Thome J R. Comprehensive thermodynamic approach to modeling refrigerant-lubricating oil mixtures [J]. HVAC & R Research, 1995, 1(2): 110-126.
  • 6ANSI/ASHRAE Standard 41.4. Standard method for measurement of proportion of lubricant of liquid refrigerant [S]. Atlanta, 1984.
  • 7Moffat R J. Describing the uncertainties in experimental results [J]. Experimental Fluid and Thermal Science, 1998(1) :3-17.
  • 8Ashok G, Michael M O, Mohsen S. In-tube condensation of refrigerant and refrigerant-oil mixtures: A review of most recent work[J]. ASHRAE Transactions, 1998, 104 (1B):1322-1332.
  • 9Bo S, Eckhard A G. A critical review of the influence of lubricants on the heat transfer and pressure drop of refrigerants: Part II. Lubricant influence on condensation and pressure drop [J]. HVAC & R Research, 2005, 11(4): 511-526.
  • 10Koyama S, Yu J. Condensation heat transfer of pure refrigerant inside an internally grooved horizontal tube[C]// Proc of the JAR Annual Conference. Japan Press, 1996:173-176.