期刊文献+

名义封闭结构风致内压的试验研究(英文)

Experimental investigation of wind-induced internal pressures in nominally sealed building structures
原文传递
导出
摘要 目的:在确保模型气密性绝对良好的前提下,通过设置不同的背景泄漏,详细研究不同背景孔隙率和风向角下的平均和峰值内压水平,为工程结构抗风设计和规范修订提供指导和依据.创新点:首次探究了完全封闭结构的内压特征,并在此基础上系统研究了不同背景孔隙率和风向角下名义封闭结构的风致内压变化规律.方法:1.在静态空气中进行压力测试,获得完全封闭结构的内压特性(图6~9).2.在完全封闭结构的表面开不同的孔隙;通过多参数风洞试验(图3和表1),获得名义封闭结构的平均和峰值风压变化特征(图14~18),并与中国建筑结构荷载规范(GB50009-2012)进行对比分析.结论:1.完全封闭结构的内压呈非平稳状态,长达9d的观察结果表明内压呈现一定的周期性.2.在均布背景孔隙下,平均内压系数仅在-0.15^-0.14范围内波动,且低于中国建筑结构荷载规范的取值-0.2.3.当峰值因子g取3.5时,最高负极值风压系数为-0.255,低于由规范计算得到的峰值内压系数-0.326. The action of internal pressure cannot be neglected in wind-resistant design of large-span structures, high-rise buildings, and low-rise residential buildings. In this study, the internal pressure characteristics were first measured in still air in a completely closed building structure without any leakage. Then a series of wind tunnel tests were conducted to study the probability density distribution characteristics of the internal pressure responses in a nominally sealed building with background leakage. The mean and peak internal pressure responses associated with different background leakage distributions and wind directions were further investigated, and the experimental results were compared with those suggested by the Chinese wind load code GB50009-2012. The results indicated that the internal pressure in the completely closed building was non-stationary, and varied significantly when collected at different time points. Furthermore, a period of about 24 h was observed from the measured time history of internal pressure over 9 d. The internal pressure in a nominally sealed building structure nearly fitted a normal Gaussian distribution. When background leakage was uniformly arranged on the surface of the building, the mean internal pressure coefficient remained unchanged with increasing background leakage, varying within the range from -0.15 to -0.14, indicating lower magnitudes than the value of -0.2 suggested by the Chinese wind load code. The minimum negative peak internal pressure coefficient was -0.255 when the peak factor was 3.5, indicating a lower magnitude than the value of -0.326 calculated in the Chinese wind load code.
出处 《Journal of Zhejiang University-Science A(Applied Physics & Engineering)》 SCIE EI CAS CSCD 2019年第7期487-498,共12页 浙江大学学报(英文版)A辑(应用物理与工程)
基金 Project supported by the Fund of State Key Laboratory of Subtropical Building Science,South China University of Technology,China(No.2019ZB28) the Key Project of Foundation and Frontier Research of Chongqing,China(No.cstc2017jcyjAX0187)
关键词 内压 风洞试验 完全封闭 背景泄漏 Internal pressure Wind tunnel experiment Completely closed Nominally sealed Background leakage
  • 相关文献

二级参考文献1

共引文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部