地震带电综合环境试验可模拟设备真实突发工况,能考核设备在地震时的安全性和可靠性,验证设备的设计并发现特殊工况中可能出现的问题和缺陷。基于某大型地震试验台,搭建了±1100kV直流电压互感器在地震带电综合环境试验中异常放电的仿真模型,分析了放电电流的峰值和频谱,研究了不同电容量试品对放电电流峰值的影响,并给出了地震台测控系统的抗干扰措施和建议。
The electricity combined environment test in earthquake band could analog the real outburst working condition of equipment,which could be used to check the security and reliability,verify the equipment design and find the possible problems and defects in special working condition.Based on certain large-scale earthquake bedstand,this paper established the simulation model of paradoxical discharge in electricity combined environment test of earthquake band for ±11 00 kV direct current potential transformer.This paper analyzed the peak and frequency spectrum of discharge current,researched on the impacts of different capacitance test object on the discharge current peak and gave the anti-jamming measures and suggestions of seismostation measurement and control system.
作者
李华良
姜明丽
庞明明
吉小振
王丁
LI Hua-liang;JIANG Ming-li;PANG Ming-ming;JI Xiao-zhen;WANG Ding(China Qiyuan Engineering Corporation,Xi’an 710018,China)
出处
《电工电气》
2019年第8期54-56,61,共4页
Electrotechnics Electric
关键词
地震试验
分布参数
放电电流
电磁干扰
earthquake test
distribution parameter
discharge current
electromagnetic interference