一起110 kV GIS电流互感器气室内部发热故障分析 被引量:7

Analysis of an Inner Heating Fault of a 110 kV GIS Current Trans Former
下载PDF
导出
摘要 针对红外测温中发现的GIS设备电流互感器气室二次回路开路导致铁芯发热的问题,结合设备结构和超声波、特高频局放检测等综合分析,提出了故障诊断依据。利用停电检查进行验证,为电流互感器二次回路开路问题的红外检测和判断提供参考。 In this paper,aiming at explaining the phenomenon of iron core overheating caused by opening secondary circuit in GIS TA chamber discovered by infrared temperature measurement,the comprehensive analysis of the equipment structure,AE and UHF detection are adopted for fault diagnosis.The off-line inspection is carried out verify the conclusion,which provides a reference for infrared detection and judgment of open circuit problem of TA secondary circuit.
作者 段辉 颜廷利 王伟 赵全富 韩明 DUAN Hui;YAN Tingli;WANG Wei;ZHAO Quanfu;HAN Ming(State Grid Laiwu Power Supply Company,Laiwu 250002,China;Economic & Technological Research Institute,State Grid Shandong Electric Power Company,Jinan 250003,China)
出处 《山东电力技术》 2019年第7期78-80,共3页 Shandong Electric Power
关键词 红外测温 GIS 电流互感器 故障诊断 infrared temperature measurement GIS current transformer fault diagnosis