期刊文献+

基于全范围模拟机对压水堆MSLB叠加SGTR事故分析 被引量:3

Analysis of Pressurized Water Reactor’s MSLB with SGTR Based on Full-scope Simulator
下载PDF
导出
摘要 主蒸汽管道断裂事故叠加蒸汽发生器传热管破裂事故属于核电厂超设计基准事故.为研究国内M310系列机组对该种事故的处理能力,采用了以宁德核电厂1号机为原型的全范围模拟机对此次事故进程进行模拟,选择了放射性释放较为恶劣的蒸汽管道破口(MSLB)叠加100根蒸汽发生器传热管破裂(SGTR)事故,并应用了最新的SOP规程中的操纵员动作以缓解事故后果,分析了事故发生后一回路压力、蒸汽发生器压力、堆芯出口温度以及一次侧至二次侧破口流量的变化.分析结果表明了在核电厂自动动作和操纵员有效及时干预下,在一定情况下可以避免进入严重事故中,最终可以处于安全可控状态. Main Steam Line Break accidentplus Steam Generator Tube Rupture accident is the beyond-design base accident of the nuclear power plant.In order to study the handing ability of domestic M310 units for this kind of accident,full scope simulator that based on Ningde Nuclear Power is adopted to simulate the accident process,accident with severe radioactive release caused by main steam line break (MSLB) overlay 100 steam generator tube rupture is selected,and controller actions stipulated in the latest SOP are applied to mitigate the consequences of the accident.The change of the primary circuit pressure,steam generator pressure,core outlet temperature and the flow rate of first-to-second-side break after the accident were analyzed.The experiment analysis shows that the nuclear power plant can finally be in a safe and controllable state under the effective and timely intervention of the nuclear power plant s automatic actions and controllers.
作者 王冠一 陈宝龙 吴鹏 郑超颖 贾伟 WANG Guanyi;CHEN Baolong;WU Peng;ZHENG Chaoying;JIA Wei(Nuclear and Radiation Safety Center,Ministry of Environmental Protection,Beijing 100082,China)
出处 《核科学与工程》 CAS CSCD 北大核心 2019年第4期613-618,共6页 Nuclear Science and Engineering
关键词 蒸汽发生器传热管破裂 主蒸汽管道破裂 全范围模拟机 SOP规程 安全可控状态 Steam Generator Tube Rupture Main Steam Line Break Full-scope simulator SOP standards Safe and controllable state
  • 相关文献

参考文献1

二级参考文献1

  • 11,RTS+ RTGV,F/9 Famille des bre'ches Sur tugauterie Secondarie accompagnees de rupture de tube de ge'ne'rateur de vapeur RTS+ RTGV

共引文献4

同被引文献23

引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部