摘要
针对老旧小区、自建房、出租房等场所设置的简易自动喷水灭火系统开展实体试验,测试三丙聚乙烯管和薄壁不锈钢管简易灭火系统的灭火效果。结果表明,薄壁不锈钢管道简易自动喷水灭火系统在火灾中自身性能稳定,没有受到火灾的破坏,及时控制并成功扑灭了火灾。PPR管道简易灭火系统不能及时控制火灾,造成火势扩大,楼梯间温度不断升高,系统管道自身被高温炙烤破坏。
Aiming at the simple auto sprinkler system in old neighborhoods,self-built houses and rented houses,full-scale test was carried out,to test the fire extinguishing effect of PPR pipe and thin-walled stainless steel pipe simple fire extinguishing system.Results showed that the thin-walled stainless steel pipe simple sprinkler system is stable in fires,won't be damaged by the fire,and can control and successfully extinguish the fire in time.PPR pipe simple sprinkler system can't control the fire on time,the fire will expanse,the temperature in the staircase will increase,and the pipe will be damaged by high temperature roasting.
作者
熊筠
李明轩
冯小军
XIONG Jun;LI Ming-xuan;FENG Xiao-jun(Sichuan Fire Research Institute of MEM,Sichuan Chengdu 610036,China)
出处
《消防科学与技术》
CAS
北大核心
2019年第7期960-962,共3页
Fire Science and Technology
基金
应急管理部四川消防研究所基本科研项目(20178808Z)
关键词
塑料管道
PPR管
薄壁不锈钢管
简易自动喷水系统
实体火实验
plastic pipes
PPR pipes
thin wall stainless steel tube
simple fire extinguishing system
full-scale fire test