宾金特高压直流保护三取二配置策略及优化研究 被引量:4

Research on Two-out-of-Three Logic Configuration Strategy and Optimization of DC Protection in Yibin-Jinhua UHVDC Project
下载PDF
导出
摘要 宾金特高压直流控制保护系统采用HCM3000硬件平台,直流保护系统同时配置了硬件三取二装置和软件三取二逻辑,正常情况下保护动作优先通过硬件三取二装置输出。针对软件三取二逻辑有效时,存在阀组保护与极保护的部分保护功能无法出口的问题,通过对直流输电系统的影响进行深入分析可知,当前设计存在导致设备故障和直流闭锁的隐患。在目前设计原理的基础上,提出了修改硬件配置和软件功能的解决措施,为现场的实际应用提供借鉴和参考。 Yibin-Jinhua UHVDC control and protection system adopts HCM3000 hardware platform.The DC protection system is equipped with two-out-of-three hardware device and software logic at the same time.Normally protective actions are preferred to exit through two-out-of-three hardware device.In view of exiting failure in some protection functions of converter protection and pole protection in the case of active two-out-of-three software logic,the paper analyzes the impact of DC transmission system and concludes that there are some potential hazards in existing design that result in device failure and DC block.Based on the current design principles,the solutions to modify the hardware configuration and software functions are put forward,which can provide a reference for the practical field application.
作者 贾轩涛 朱玉婷 陈剑飞 薛鑫新 黄华 JIA Xuantao;ZHU Yuting;CHEN Jianfei;XUE Xinxin;HUANG Hua(State Grid Zhejiang Maintenance Branch Company,Hangzhou 311232,China)
出处 《浙江电力》 2019年第9期105-110,共6页 Zhejiang Electric Power
关键词 特高压直流输电 直流保护 三取二逻辑 直流闭锁 保护跳闸 UHVDC DC protection two-out-of-three logic DC block protection trip