超高压变电站二次抗干扰措施排查与整改

Investigation and Rectification of Secondary Anti-interference Measures for Ultra-high Voltage Substation
下载PDF
导出
摘要 梳理了现阶段南方电网公司对变电站二次抗干扰措施的要求。从室内、室外二次接地网及其连接部分着手,详细说明了某超高压变电站实际排查情况及整改措施。提出根本的排查思路是全站应形成二次等电位接地网。整改后的变电站二次接地网效果良好,保护运行平稳。 This paper introduces the requirements of China Southern Power Grid Company on the secondary anti-interference measures for substation in the current stage. It sets out from the indoor and outdoor grounding networks and their connection parts, introduces in detail the the actual inspection situation and rectification measures of the specific substation, suggesting that the basic troubleshooting idea is to form an equipotential grounding network of the whole substation. The modification of secondary grounding network of the substation has obtained good effectiveness, which ensures the smooth operation.
作者 王荣超 WANG Rongchao(China Southern Power Grid EHV Transmission Corporatron Liuzhou Bureau, Liuzhou 545006, Guangxi ZhuangAutonomous Region, China)
出处 《电力安全技术》 2019年第8期61-64,共4页 Electric Safety Technology
关键词 超高压变电站 二次系统 等电位接地网 抗干扰 排查 整改 UHV substation secondary system equipotential grounding network anti-interference troubleshooting rectification