220kV断路器储能机构异常分析及对策 被引量:4

Abnormal analysis and countermeasure of 220kV circuit breaker energy storage mechanism
下载PDF
导出
摘要 本文针对某燃机电厂220kV气体绝缘封闭开关设备3年中多次发生断路器液压弹簧操纵机构内漏,由于发现不及时,造成运行和检修非常被动的情况,对断路器储能机构及二次回路详细检查、分析,最终确认在储能电机回路加装计数器,及早发现设备异常,及时进行处理。 Regarding the leakage of hydraulic spring control mechanism of circuit breaker in 220kV gas insulated switchgear equipment of a gas turbine power plant in the past three years,because discovery is not in time,cause operation and overhaul very passive circumstance.Detailed inspection and analysis of the circuit breaker energy storage mechanism and secondary circuit,and finally confirm to install the counter in the energy storage motor circuit,find the abnormal equipment as early as possible,and deal with it in time.
作者 李鲲 Li Kun(Jiangsu Huadian Qishuyan Power Generation Co.,Ltd,Changzhou,Jiangsu 213011)
出处 《电气技术》 2019年第10期107-109,共3页 Electrical Engineering
关键词 断路器 液压弹簧操纵机构 储能电机 计数器 circuit breaker hydraulic spring control mechanism energy storage motor counter