期刊文献+

干式铁心并联电抗器附加绕组故障分析及设计改进

Fault Analysis and Improving Design of Auxiliary Winding for Dry-type Iron Core Shunt Reactor
下载PDF
导出
摘要 某干式铁心并联电抗器运行时发生故障,附加绕组出现匝间短路问题,导致故障停机。通过对附加绕组安装运行环境和温升过程进行分析,找出了故障原因,并改进了结构设计。计算验证表明:改进后的结构避免了附加绕组温升异常,提高了产品可靠性。 Some dry-type iron core shuntreactor got fault at run time,interturn short circuit of the auxiliary winding happened,which led to failure of running.Through analysis of running condition and temperature rise process,the reasons of failure were found,and the structure design was improved.Calculation indicated the improved structure solved the problem of temperature rise of auxiliary winding,then the reliability of dry-type iron core shuntreactor was enhanced effectively.
作者 马志钦 毛启武 杨贤 孙文星 周丹 MA Zhiqin;MAO Qiwu;YANG Xian;SUN Wenxing;ZHOU Dan(Electric Power Research Institute of Guangdong Power Grid Co.Ltd.,Guangzhou 510600,China;Pearl Electric Co.,Ltd.,Guangzhou 511400,China)
出处 《机电工程技术》 2019年第9期233-234,264,共3页 Mechanical & Electrical Engineering Technology
基金 广东电网有限责任公司科技项目(GDKJXM20162143)
关键词 干式铁心并联电抗器 附加绕组 匝间短路 温升 结构设计 dry-type iron core shunt reactor auxiliary winding inter turn short circuit fault temperature rise structure design
  • 相关文献

参考文献9

二级参考文献42

共引文献35

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部