摘要
结合国家标准GB 50116-2013《火灾自动报警系统设计规范》及相关地方规定,探讨火灾自动报警系统形式的选择、设备的设置、建筑物特殊部位火灾自动报警系统设计、消防设备配电系统电源监控采集点的设置等问题,并给出作者的建议。对规范在建筑电气设计中如何贯彻、容易忽略的条文,以及具体工程项目中规范未涉及的问题,提出相应的解决方案。
In accordance with the Code for Design of Automatic Fire Alarm System(GB 50116-2013)and relevant local regulations,the issues related to the selection of alarm system type and equipment layout,system design at special parts of buildings,and settings of collection point of monitoring on power distribution system of firefighting apparatus are discussed with suggestions given by the author.Solutions are proposed for the implementation of overlooked provisions in the specification and issues not covered by the specific works.
作者
陈技
林洪钟
黄园梅
CHEN Ji;LIN Hongzhong;HUANG Yuanmei(Fujian Provincial Institute of Architectural Design and Research Co.,Ltd.,Fuzhou 350001,China)
出处
《建筑电气》
2019年第10期39-47,共9页
Building Electricity
关键词
消防控制室
探测器
消防水泵房
电源监视
防排烟风机房
雨淋阀组
消防模块
双电源互投
fire control room
detector
fire-fighting water pump house
power monitoring
smoke-proof and exhaust fan room
deluge valves unit
fire control module
double power mutual switching