摘要 以采用嵌管式外墙的上海办公空调房间为研究对象,利用DesignBuilder软件建立空调结合辐射墙体模型,模拟分析夏季南向外墙增加布置嵌管后其内壁面温度和热舒适指标PMV-PPD的变化趋势,评估采用该种组合空调方式的节能潜力。研究结果表明,增加嵌管后,嵌管式外墙内壁面温度呈现显著降低趋势,影响嵌管式外墙性能的主要因素为进水温度。在满足90%PMV低于1的前提下,本文研究的空调器搭配嵌管式外墙辐射系统室内设计温度可以提高1℃。 Taking offices with air conditioner and embedded pipe wall in Shanghai as study object,the model combined with air conditioner and radiation surface is built up using DesignBuilder.The change trends in summer of the internal wall temperature and thermal comfort index PMV-PPD of the south-facing wall embedded with pipes are analyzed,and the energy-saving potential for this type of combined air-conditioning is estimated.The research results show that the internal wall temperature of the wall with embedded pipe significantly reduces,and the key performance impacting factor is inlet water temperature.On the condition that 90%of PMV is lower than 1,the design temperature of room using air conditioner combined with radiation system of exterior wall with embedded pipes can be increased by 1℃.
作者 赵德印 潘黎 范宏武 徐强 Zhao Deyin;Pan Li;Fan Hongwu;Xu Qiang(Shanghai Research Institute of Building Sciences(Group)Co.,Ltd.;College of Civil Engineering,Tongji University;Shanghai Research Institute of Building Sciences)
出处 《制冷与空调》 2019年第10期82-87,共6页 Refrigeration and Air-Conditioning
基金 国家重点研发计划项目“长江流域建筑供暖空调解决方案和相应系统”(2016YFC0700302)
关键词 空调 辐射换热 PMV-PPD 嵌管式外墙 热舒适 节能 air-conditioning radiation heat transfer PMV-PPD exterior wall with embedded pipes thermal comfort energy-saving
  • 相关文献

参考文献2

二级参考文献24

  • 1邱林,刘肇生,裴立德,王文海.采用预应力空心楼板与干式地面结构的地板采暖的可行性研究[J].建筑科学,2005,21(3):44-47. 被引量:5
  • 2韩荣山,由世俊,王海霞.板式地板辐射供暖系统传热性能模拟研究[J].煤气与热力,2006,26(7):70-73. 被引量:2
  • 3Fontana L. Thermal performance of radiant heating floors in furnished enclosed spaces [ J ]. Applied Thermal Engineering, 2011,31 : 1547-1555.
  • 4Lu Shikui, Zhang Xiaosong. Thermal comfort assess- ment and energy consumption analysis of ground-source heat pump system combined with radiant heating/cool- ing [ J ]. Journal of Southeast University,2012,28 ( 1 ) : 52-57.
  • 5Ehab Foda, Kai Siren. Design strategy for maximizing the energy-efficiency of a localized floor-heating system using a thermal manikin with human thermoregulatory control [ J ]. Energy and Buildings, 2012,51 : 111-121.
  • 6Birol Kilkis. Exergy metrication of radiant panel heat- ing and cooling with heat pumps [ J]. Energy Conver- sion and Management,2012,63: 215-224.
  • 7Dongliang Zhang, Ning Cai, Zijie Wang. Experimental and Numerical Analysis of Lightweight Radiant Floor Heating System [ J ]. Energy and Buildings, 2013,61 : 260-266.
  • 8Gebhart B. Surface temperature calculations in radiant surroundings of arbitrary complexity--for gray, diffuse radiation [ J ]. International Journal of Heat and Mass Transfer, 1961,3 ( 4 ) : 341-346.
  • 9Yoshihito Kurazumi, Tadahiro Tsuchikawa, Jin Ishii, et al. Radiative and convective heat transfer coefficients of the human body in natural convection [ J ]. Building and Environment,2008,43:2142-2153.
  • 10Buratti C, Ricciardi P, Vergoni M. HVAC systems tes- ting and cheek: A simplified model to predict thermal comfort conditions in moderate environments [ J ]. Ap- plied Energy,2013,104 : 117-127.