期刊文献+

关于渗透通风条件下室内PM2.5净化过滤负荷计算相关设计参数探讨 被引量:1

Determination on the Calculation and Key Design Parameters of Indoor PM2.5 Filtration Load Under the Condition of Building Infiltration
原文传递
导出
摘要 大量实测结果表明,即使关闭建筑外窗,室外细颗粒物(即PM2.5)仍可跟随建筑外窗缝隙渗透通风进入室内,污染室内环境。合理评估室内PM2.5净化过滤负荷对空气净化器设计选型有重要指导意义。研究团队前期提出了基于渗透通风条件下室内PM2.5净化过滤负荷计算模型,然而,模型中房间换气次数和细颗粒物穿透系数难以简单确定,尚未给出推荐设计值,限制了模型的工程应用价值。为此,本文结合研究团队前期提出的房间换气次数、PM2.5穿透系数与沉降率推算模型,以及北京地区多个办公建筑室内外PM2.5质量浓度和室外气象参数长期监测结果,研究并提出了基于渗透通风条件下,不同气密性等级建筑外窗对应的单位缝长渗透通风量和穿透系数确定方法,给出了推荐设计值,评估了建筑外窗气密性等级对空气净化器净化寿命的影响。 Field measurement results reveal outdoor PM2.5 can still go indoors through building infiltration even all the windows and doors are closed.An accurate evaluation of indoor PM2.5 filtration load will provide great help on designing an efficient indoor air filtration device.A calculation model of indoor PM2.5 filtration load has been proposed by the authors in previous studies.However,in this model,some important parameters,such as air change rate and particle penetration factor,are too complex to obtain and the recommend design values for engineering application were not proposed.Therefore,a determination method of the two parameters was proposed in this study,based on the relevant parameters’calculation models developed by the authors previously and the long-term field measurement database of indoor-outdoor PM2.5 mass concentrations and outdoor meteorological parameters in Beijing,China.The recommend design values of the two parameters under various external window air-tightness levels were provided.Additionally,the influence of the external window air-tightness level on cleaning life span of air filters were evaluated.
作者 陈紫光 陈超 曹国庆 邬艳 吴玉琴 刘子嘉 朱娟花 张铭健 李炫 CHEN Ziguang;CHEN Chao;CAO Guoqing;WU Yan;WU Yuqin;LIU Zijia;ZHU Juanhua;ZHANG Mingjian;LI Xuan(Institute of Building Environment and Energy Efficiency,China Academy of Building Research,Beijing 10013,China;Key Laboratory of Green Built Environment and Energy Efficient Technology,Beijing University of Technology,Beijing 100124,China;CAUPD Beijing Planning&Design Consultants Co.,Beijing 100044,China;Chalone Smart Technology Co.,Ltd.,Beijing 100015,China)
出处 《建筑科学》 CSCD 北大核心 2019年第10期163-169,共7页 Building Science
基金 “十三五”国家重点研发计划项目“室内微生物污染源头识别监测和综合控制技术”(2017YFC0702800
关键词 大气PM2. 5污染 建筑渗透通风 PM2. 5净化过滤负荷 净化寿命 设计参数 建模与实测 outdoor PM2.5 pollution building infiltration indoor PM2.5 filtration load cleaning life span design parameters,mathematical model and field measurement
  • 相关文献

参考文献12

二级参考文献126

共引文献215

同被引文献9

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部