摘要 某220 kV变电站相继发生两起35 kV站用干式变压器相间短路跳闸事故,发生事故的站用变均为采用接地铜屏蔽层的新结构干式变压器。对这种干式变压器的性能进行研究,并分析了其他新型结构干式变压器的优缺点。 A 220 kV substation has two phase-to-phase short-circuit tripping accidents for dry-type transformers.The fault transformers are grounded with copper shielding layer on the inside of high-voltage coils.In this paper,the performance of this dry-type transformer was studied,and the advantages and disadvantages of some other new-structure dry-type transformers were also analyzed.
作者 董政 王小朋 牛丽丽 刘常军 金卫军 杜岳凡 DONG Zheng;WANG Xiaopeng;NIU Lili;LIU Changjun;JIN Weijun;DU Yuefan(State Grid Tianjin Power Maintenance Company,Tianjin 300000,China)
出处 《电工技术》 2019年第21期128-129,131,共3页 Electric Engineering
关键词 干式变压器 相间短路 接地铜屏蔽层 散热 局部发电 dry-type transformer phase-to-phase short circuit grounded copper shielding layer heat dissipation partial discharge