期刊文献+

频域谱技术用于油浸式电力变压器绝缘状态现场诊断

Frequency Domain Spectrum Technique for On-site Diagnosis of Oil-immersed Power Transformer Insulation state
下载PDF
导出
摘要 为提高油浸式电力变电器运行的可靠性,本文提出基于频域谱技术的绝缘状态诊断方法。以220 kV变压器为研究对象,通过对比频域谱技术测量法与预防性试验法的测试数据,以验证两种方法对于变压器电容测量结果的一致性。结果显示,频域谱技术可以准确地反映变压器绝缘中的水含量,为绝缘状态诊断提供有价值的参考信息。频域谱技术属于一种无损测试方法,可以有效地进行油浸式电力变压器绝缘状态诊断。 In order to improve the reliability of oil-immersed power transformers,this paper proposes an insulation state diagnosis method based on spectrum technology.Taking the 220 kV transformer as the research object,the test data of the frequency domain spectrum measurement method and the preventive test method are compared to verify the consistency of the two methods in the transformer capacitance measurement results.The results show that the frequency domain spectrum technique can accurately refl ect the water content in the transformer insulation and provide valuable reference information for the insulation state diagnosis.Therefore,the frequency domain spectrum technique belongs to a non-destructive test method,which can effectively diagnose the insulation state of the oil immersed power transformer.
作者 李敏 Li Min
出处 《电力系统装备》 2019年第21期133-134,共2页 Electric Power System Equipment
关键词 频域谱 油浸式变压器 绝缘 诊断 frequency domain spectrum oil-immersed transformer insulation diagnosis
  • 相关文献

参考文献3

二级参考文献17

  • 1钱政.大型电力变压器绝缘故障诊断中人工智能技术的应用研究[M].西安:西安交通大学,2000..
  • 2Emsley A M,Xiao X,Heywood R J,et al.Degradation of cellulosic insulation in power transformers,part 2:formation of furan products in insulating oil[J].IEE Proceedings Science Measurement & Technology,2000,147(3):110-114.
  • 3Zhang C H,Macalpine J M K.Furfural concentration in transformer oil as an indicator of paper ageing,part 1:a review[C].Power Systems Conference and Exposition.Latin America,2006:1088-1091.
  • 4Allan D.Recent advances in the analysis and interpretation of aged insulation from operating power transformers[C].Proceedings of the 5th International Conference.Seoul,South Korea,1997:202-205.
  • 5Hill D J T,Le T T,Darveniza M,et al.Degradation of cellulosic insulation materials in a power transformer part3:degradation products of cellulose paper insulation[J].Polymer Degradation and Stability,1996,51(2):211-218.
  • 6Blue R,Uttamchandani D.Infrared detection of transformer insulation degradation due to accelerated themal aging[J].IEEE Trans on D&EI,1998,5(2):165-168.
  • 7Shroff D H,Stannett A W.Review of paper ageing in power transformers[J].IEE Proc C,1985,132(6):312-319.
  • 8Burton P J,Carballiera M,Duval M,et al.Applications of liquid chromatography to the analysis of electrical insulating materials[C].Proceeding of the CIGRE Conference.Paris,1988:15.
  • 9Pablo A De.Interpretation of degradation models of furanic compounds[C].Proceeding of the CIGRE Conference.Melbourne,Australia,1997:15.
  • 10DL/T984-2005 油浸式变压器绝缘老化判断导则[S],2005.