基于多种试验综合诊断的CVT电压异常故障分析 被引量:8

Analysis of CVT Voltage Abnormal Fault Based on Comprehensive Diagnosis of Multiple Tests
下载PDF
导出
摘要 介绍110 kV母线CVT电压异常故障,通过分析CVT电气试验数据、绝缘油耐压、微水及色谱试验数据判断CVT内部存在电弧放电现象。通过解体检查,电容器单元有游离碳存在,中压电容元件有烧蚀碳化痕迹,中间变压器一次绕组存在电弧、过热痕迹,验证了试验数据分析的正确性。 In this paper,a fault of CVT voltage abnormality on a 110 kV busbar is introduced.By analyzing the electrical test data of CVT,the withstand voltage of insulating oil,the micro water and the chromatographic test data,it is concluded that the arc discharge exists in the CVT.By disintegration inspection,the capacitor unit is contaminated by free carbon.The medium voltage capacitors have ablation carbonization traces.It is also found that the primary transformer has arc and overheat traces in the primary winding,which verifies the correctness of the test data analysis.
作者 王政 郭峰 杨锟 赵恒伟 马霄霖 WANG Zheng;GUO Feng;YANG Kun;ZHAO Hengwei;MA Xiaolin(State Grid Binzhou Power Supply Company,Binzhou 256600,China)
出处 《山东电力技术》 2019年第11期60-63,共4页 Shandong Electric Power
关键词 电容式电压互感器 电压异常 电气试验 油耐压试验 微水检测 色谱分析 CVT voltage anomaly electrical test oil pressure test micro water test chromatographic analysis