期刊文献+

一起220 kV母线故障保护动作分析与讨论 被引量:3

Analysis and Discussion of a 220 kV Bus Fault Protection Action
下载PDF
导出
摘要 某电厂检修人员敷设测试线进行主变电度表二次压降测试过程中,因测试线摆动导致升压站220 kV母线通过测试线对网控室窗台放电,造成母线接地故障。文章结合事故现场检查结果,保护动作情况和RCS-915AS型、WMH-800型母线保护装置技术说明书,对事故发生的原因、母线保护装置、保护动作过程等进行了分析与讨论,并针对此次事故提出了改进意见,以提高设备可靠性。 When a power plant maintenance person laid a test line to test the secondary voltage drop of the main transformer meter,the 220 kV bus of the booster station discharged through the test line to the window room of the network control room due to the swing of the test line,causing the bus ground fault.Combined with the accident site inspection results,protection actions and technical specifications of the RCS-915AS and WMH-800 busbar protection devices,the causes of the accident,the busbar protection device and the protection action process were analyzed and discussed.The improvement suggestions were put forward for the accident to improve the reliability of the equipment.
作者 曾云林 ZENG Yunlin(Guangzhou Development Taiping Distributed Energy Station Co.,Ltd.,Guangzhou 510990,China)
出处 《电工技术》 2019年第22期108-110,共3页 Electric Engineering
关键词 母线保护 差动保护 死区保护 失灵保护 保护双重化 busbar protection differential protection dead zone protection failure protection double protection
  • 相关文献

参考文献3

二级参考文献14

共引文献16

同被引文献32

引证文献3

二级引证文献7

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部