期刊文献+

特高压断路器近区故障合成试验用人工数学链路设计研究 被引量:1

Artificial Mathematics Link Design Research Used in EHV Circuit Breaker Close-In Fault Synthetic Test
下载PDF
导出
摘要 近区故障开断特性是断路器型式试验中的重要考核项目。就模拟一段架空线路的人工数学链路进行了研究及设计,介绍了人工数学链路设计及选型,对链路结构设计进行了阐述,并从人工数学链路的原理结构、参数计算、元器件选型以及过电压分析等方面进行了仿真计算,最终设计出了满足800kV/63kA整极、1200kV/80kA半极近区故障试验要求的人工数学链路,并且与实际架空线路有较好的等价性。 The close-in fault making and breaking characteristic is the important evaluation indicator in circuit breaker type tests.A length of overhead line of artificial mathematics link was simulated to carry out research and design.Introduction was made to the artificial mathematics link design and selection.This paper expounded the link structure design and carried out simulated calculation from the aspects of principle structure of artificial mathematics link,parameter calculation,components selection and overvoltage,and designed the artificial mathematics link meeting the requirement of 800 kV/63 kA whole polarity,1200 kV/80 kA half polarity close-in fault tests,closely equivalent to the practical overhead line.
作者 瞿哲奕 洪深 陈勇 郑占锋 周文杰 张玲 QU Zhe-yi;HONG Shen;CHEN Yong;ZHENG Zhan-feng;ZHOU Wen-jie;ZHANG Ling(State Grid Electric Power Research Institute,Nanjing 211000,China;State Grid Power Testing and Certification Technology Co.,Ltd,Nanjing 211000,China)
出处 《电工电气》 2019年第12期53-58,共6页 Electrotechnics Electric
关键词 近区故障 人工数学链路 合成试验 元件选型 过电压分析 close-in fault artificial mathematics link synthetic test components selection overvoltage analysis
  • 相关文献

参考文献1

二级参考文献5

  • 1王仁甫.阻尼的Ⅱ型人工链路的特性及其应用.高压电器,1984,20(1):94-94.
  • 2金立湘.近区故障问题.高压电器,1980,16(5):74-74.
  • 3曹荣江.关于“近区故障”的计算方法.高压电器,1979,15(4):64-64.
  • 4VAN DER LINDEN W A, VAN DER SLUIS L. A New Artificial Line for Testing High-voltage Circuit Breakers[J]. IEE PAS-102, 1983(4): 797-803.
  • 5金立湘.近区故障合成试验的一些问题[J].高压电器,1983,19(1):12-19.