期刊文献+

基于动态电阻技术SF6断路器灭弧室发热缺陷分析与处理 被引量:6

Analysis Treatment of Heat Fault Treatment for SF6 Circuit Breaker Arc Extinguish Chamber Based on Dynamic Resistance Technology
下载PDF
导出
摘要 本文基于动态电阻技术对一起SF6断路器灭弧室发热缺陷进行了详细分析,介绍动态电阻测试基本原理,利用动态电阻技术评估灭弧室发热严重程度,判断发热是否已影响断路器弧触头灭弧性能,并通过灭弧室解体进行验证,最后对SF6断路器灭弧室发热缺陷状态评估提出建议。 Based on the dynamic resistance technology, this paper analyzes a heating defect of arc extinguishing chamber of SF6 circuit breaker in detail, introduces the basic principle of dynamic resistance testing, and uses the dynamic resistance technology to evaluate the heating degree of arc-extinguishing chamber whether the heating has affected the arc extinguishing performance of the arc extinguishing contact of the circuit breaker, and the fault is verified by the disintegration of the arc extinguishing chamber.Finally, some suggestions are put forward for the condition evaluation of the heating defect in the arc extinguishing chamber of SF6 circuit breaker.
作者 汪佳 范敏 张超 WANG Jia;FAN Min;ZHANG Chao(China Energy Engineering Group Co.,Ltd.,Hunan Electric Power Design Institute Corporation Limited,Changsha 410007,China;State Grid Hunan Electric Power Company Limited Research Institute,Changsha 410007,China;State Grid Yueyang Power Supply Company,Yueyang 414000,China)
出处 《湖南电力》 2019年第6期57-60,共4页 Hunan Electric Power
关键词 动态电阻 SF6断路器 灭弧室 状态评估 dynamic resistance SF6 circuit breaker arc extinguish chamber state evaluation