摘要 本文基于DeST软件和冷水机组全工况性能曲线,采用逐时能耗模拟方法,对主机分别为定频螺杆式冷水机组和永磁同步变频螺杆式冷水机组的地铁站制冷机房进行全年能耗模拟。结果表明,主机为永磁同步变频离心机的制冷机房系统综合能效比(EER)达到6.1,相对于主机为定频螺杆式冷水机组的制冷机房系统节能率为27.5%。相同工况下,主机为永磁同步变频螺杆式冷水机组的制冷机房节能优势明显。 Based on the De ST software and full working condition performance curves of chillers, the hourly energy consumption simulation is conducted for a cooling station with fixed-frequency screw chillers and the permanent-magnet synchronous variable-frequency screw chillers, respectively in a subway station. The results showed that the system integrated energy efficiency ratio(EER) of the cooling station with permanent-magnet synchronous variable-frequency screw chillers is reached 6.1, and the system energy saving is reached 27.5% compared with the cooling station with fixed-frequency screw chillers. Therefore, energy-saving advantages of the cooling station with the permanent-magnet synchronous variable-frequency screw chillers is more obvious under the same working conditions.
作者 卓明胜 王升 韩广宇 何玉雪 ZHUO Mingsheng;WANG Sheng;HAN Guangyu;HE Yuxue(State Key Laboratory of Air-Conditioning Equipment and System Energy Conservation,Zhuhai,Guangdong 519070,China;GREE Electric Appliances,Inc.of Zhuhai,Zhuhai,Guangdong 519070,China)
出处 《制冷技术》 2019年第5期72-77,共6页 Chinese Journal of Refrigeration Technology
关键词 能耗仿真 永磁同步 变频 螺杆式 系统综合能效比 节能 Energy simulation Permanent-magnetic synchronous Variable-frequency Screw chillers Energy efficiency ratio Energy saving
  • 相关文献

参考文献15

二级参考文献80

共引文献69

同被引文献66

引证文献6

二级引证文献15

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部