摘要 根据发电机漏氢量超标的危害,对某厂210 MW机组刚大修后开机正常运行不久就发生发电机漏氢的现象进行分析,经判断是内环导电螺钉偏离孔中心,致使密封垫压偏,气体逸出,导致导电螺钉密封不良。因此,解体检修中不能忽略的隐患密封点,即密封“死点”的安装工艺。从发电机安装、检修、运行等方面提出了9个防范措施,并根据其原因和处理过程对今后的发电机检修提出了相应的预防措施,确保发电机的安全稳定运行。 According to the hazards of excessive hydrogen leakage from generators,the phenomenon of hydrogen leakage from generators occurred shortly after the normal operation of the 210 MW unit of a certain factory was started after the overhaul.After investigation,it was judged that the conductive screw of the inner ring deviated from the center of the hole,resulting in seal cushion pressure.Offset,gas escape,lead to conductive screw seal poor,through this analysis,attention is paid to some of the hidden dangers that are easily overlooked in the overhaul,seal"dead point",and require that you should not ignore the installation process of these points because of the pursuit of progress.Nine preventive measures were put forward from the aspects of generator installation,overhaul and operation,and corresponding preventive measures were put forward according to the reasons and treatment process to ensure the safety and stability of generator operation.
作者 彭航宇 PENG Hangyu(National Electric Investment Group Jiangxi Electric Power Co.,Ltd.Fenyi Power Plant,Xinyu 336607,Jiangxi,China)
出处 《能源研究与管理》 2019年第4期97-100,共4页 Energy Research and Management
关键词 氢冷发电机组 内冷水系统 漏氢 分析处理 hydrogen cooling generator set internal cold water system hydrogen leakage analysis and processing
  • 相关文献

参考文献4

二级参考文献5

  • 1何德兆.氢冷发电机漏氢量测试及计算中的几个问题[J]电力建设,1985(04).
  • 2吴惠庭.荆门热电厂五号发电机漏氢量测定可靠性分析[J]大电机技术,1984(04).
  • 3李伟清.汽轮发电机故障检查分析及预防[M]北京:中国电力出版社,2002.
  • 4上海汽轮机发电有限公司.大型氢冷汽轮发电机及无刷励磁机组安装工艺导则[S].1998.
  • 5国电铜陵发电有限公司.电气设备及系统[S].2007.