期刊文献+

抽水蓄能电站喷淋系统潜水泵电动机绝缘性能下降原因分析

Analysis on Insulation Property Degradation of Electric Motor for Submersible Pump in Spray System of Pumped-Storage Power Station
下载PDF
导出
摘要 对内蒙古呼和浩特抽水蓄能电站上水库面板喷淋系统取水泵电动机绝缘下降原因进行分析,确认上水库水位大幅度变化使取水泵工作扬程超出设计扬程,电动机过热或长时间低功率运行,造成电动机绝缘性能下降;取水泵在越冬期一直处在深水中,受环境影响也造成电动机绝缘性能下降。为此提出在原取水泵启停逻辑中增加取水泵切换功能,在取水泵管路系统中增加越冬期取水泵空载运行管路等措施。实施后,取水泵电动机绝缘性能下降问题基本解决。 This paper analyzes the reasons for the insulation decline of the electric motor for the water intake pump in the panel spray system of the upper reservoir in Inner Mongolia Hohhot Pumped-Storage Power Station.The working head of water intake pump exceeds the design head due to the large variation of water level in upper reservoir.The insulation property decline is caused by overheating and prolonged low power operation of the electric motor.The water intake pump has been in deep water during the winter,therefore,the environment factor is another reason.It is proposed to add a switching logic to the start stop logic of the water intake pump,and add no-load operation pipe tubing for it in winter.The insulation performance degradation of the electric motor has been solved by using the measures presented above.
作者 毛宇洛 吴志刚 张东东 郭家兴 崔景源 MAO Yuluo;WU Zhigang;ZHANG Dongdong;GUO Jiaxing;CUI Jingyuan(Yangtze Ecology and Environment Co.,Ltd.,Wuhan 430062,China;Inner Mongolia Hohhot Pumped-Storage Power Generation Co.,Ltd.,Hohhot 010051,China)
出处 《内蒙古电力技术》 2019年第6期55-58,共4页 Inner Mongolia Electric Power
关键词 抽水蓄能电站 喷淋系统 潜水泵 电动机 绝缘性能 水泵扬程 pumped-storage power station spray system submersible pump electric motor insulation property pump head
  • 相关文献

参考文献5

二级参考文献8

共引文献11

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部