摘要
为了研究现场工况GIS(气体绝缘金属封闭开关)运行过程中水分对尖端放电缺陷下SF6气体分解产物的影响,在252 k V真型GIS故障仿真实验平台基础上构建了SF6气体分解产物检测系统,通过短时连续局部放电实验,得到GIS腔室内部在尖端放电缺陷下CO,CO2,CF4,C2F6等SF6分解产物随微水含量的变化规律。结果表明:在现场工况尖端放电缺陷短时连续监测下,随着放电时间的增加,在高微水情况下φ(CO2)明显高于低微水情况,而φ(C2F6)受水分影响较小,整体增加范围在700×10-6~1000×10-6,可以用这2种产物来表征GIS内部尖端放电缺陷的产生;φ(CO)与φ(CF4)在不同微水含量条件下,随放电时间的增加波动较大,并无明显变化规律,可以作为尖端放电缺陷的辅助判据。
To study the effect of moisture on SF6 decomposition products in the operation of GIS in field operating condition,an SF6 decomposition products detection system was constructed on 252 k V GIS fault simulation and experiment platform.Through short-term continuous partial discharge,it is concluded that SF6decomposition products such as CO,CO2,CF4 and C2F6 vary with micro-water under point discharge in GIS chamber.The result shows that under the short-term continuous monitoring of the point discharge defects,φ(CO2)of high micro-water is more than that of low water content with the increase of discharge time whileφ(C2F6)is less affected by moisture,and the overall increase range is 700×10-6~1000×10-6.These two products can characterize the generation of point discharge defects in GIS;under different micro-water contents,φ(CO)andφ(CF4)fluctuate greatly with discharge time increase,and there is no obvious rule,which can be used as auxiliary judging criteria for point discharge defects.
作者
王绍安
何彦良
邵先军
徐华
沈智伟
孙安邦
张冠军
WANG Shaoan;HE Yanliang;SHAO Xianjun;XU Hua;SHEN Zhiwei;SUN Anbang;ZHANG Guanjun(State Grid Zhejiang Electric Power Research Institute,Hangzhou 310014,China;State Key Laboratory of Electrical Insulation and Power Equipment,Xi'an Jiaotong University,Xi'an 710049,China;State Grid Zhejiang Electric Power Co.,Ltd.,Hangzhou 310007,China)
出处
《浙江电力》
2019年第12期87-92,共6页
Zhejiang Electric Power
基金
国网浙江省电力有限公司科技项目(5211DS170012)
关键词
GIS
尖端放电
六氟化硫
微水含量
分解组分
GIS
point discharge
SF6
micro-water content
decomposition components