摘要
分析低压出线回路短路造成10 kV高压断路器越级跳闸的原因,并给出了相应的整改措施.除了对断路器整定值及跳闸时间适当调整,保证其选择性分断,还需根据工艺流程对变压器负荷进行分组整合,以减小停电范围,保证生产的顺利进行.
This paper analyzes the reason of overriding trip of 10kV high voltage circuit breaker caused by short circuit of low-voltage outlet circuit,and put forward the corresponding rectification measures.In addition to adjusting the setting value and tripping time of the circuit breaker to ensure the selectivity,the load of the transformer is also grouped and integrated according to the process flow to reduce the power outage range and ensure the smooth progress of production.
作者
张兵
桂腾跃
裴勇
秦永昌
ZHANG Bing;GUI Tengyue;PEI Yong;QIN Yongchang(No.4 Engineering Dept.,SIPPR Engineering Group Co.,Ltd,Zhengzhou 450007,China;Ningbo Cigarette Factory,China Tobacco Zhejiang Industrial Co.,Ltd,Ningbo 315000,China;Xuchang Cigarette Factory,China Tobacco Henan Industrial Co.,Ltd,Ningbo 461000,China;Anyang Cigarette Factory,China Tobacco Henan Industrial Co.,Ltd,Anyang 455000,China)
出处
《成组技术与生产现代化》
2019年第3期42-45,共4页
Group Technology & Production Modernization
关键词
越级跳闸
选择性
分组供电
供电可靠性
skip jumping brake
selectivity
packet power supply
power supply reliability