期刊文献+

铜冶炼厂可燃和有毒气体检测报警设计探讨 被引量:2

Discussion on the Design of Combustible and Toxic Gas Detection and Alarm in Copper Smelter
下载PDF
导出
摘要 铜冶炼厂涉及较多可燃、有毒气体,本文探讨了典型铜冶炼厂的可燃和有毒气体检测报警设计,给出了高报值的设计参考值,即二氧化硫、砷化氢、硫化氢、氯气高报值最大分别为27 mg/m^3、0.54 mg/m^3、38 mg/m^3、5.8 mg/m^3。 There are many combustible and toxic gases in copper smelter.This paper discusses the design of combustible and toxic gases detection and alarm in a typical copper smelter,and gives the design reference values of high reported values,that is,the maximum reported values of sulfur dioxide,hydrogen arsenide,hydrogen sulfide and chlorine gas are 27 mg/m^3,0.54 mg/m^3,38 mg/m^3 and 5.8 mg/m^3 respectively.
作者 杜龙 周天驰 孔新红 DU Long;ZHOU Tianchi;KONG Xinhong(China Nerin Engineering Technology Co.,Ltd.,nanchang 330038,China)
出处 《有色冶金设计与研究》 2019年第6期105-108,共4页 Nonferrous Metals Engineering & Research
基金 2016年江西省创新驱动“5511”工程(20165ABC28005)
关键词 铜冶炼 可燃气体 有毒气体 检测 报警值 copper smelting combustible gas toxic gas detection alarm value