摘要 煤气电厂采用的海水直流冷却水系统属于大流量低扬程供水系统,易发生水锤事故。采用美国AFT公司Impules6压力系统水锤分析程序,模拟该系统主要设备的工作过程,进行停泵水锤分析。选择在泵站出口管道上设置调压井,可有效保障海水直流冷却水系统的安全稳定运行。 The seawater direct flow cooling water system used in gas power plant is a water supply system with large flow and low lift,which is prone to water hammer accidents.Using the water hammer analysis program of impales 6 pressure system of American AFT company,the working process of the main equipment of the system is simulated,and a pump stop water hammer analysis is carried out.The set up of a surge tank on the outlet pipe of pump station can effectively guarantee the safe and stable operation of the seawater direct cooling water system.
作者 刘军 赵越 刘自力 LIU Jun;ZHAO Yue;LIU Zili(Hunan Electric Power Design Institute Co.,Ltd of China Energy Engineering Corporation,Changsha,Hunan 410007,China)
出处 《冶金动力》 2020年第2期59-63,67,共6页 Metallurgical Power
关键词 火电厂 大流量低扬程 供水系统水锤防护 直流冷却水 thermal power plant large-flow and low-lift water supply system waterhammer protection of water supply system direct-flow cooling water