期刊文献+

基于Trnsys的某数据中心能耗分析 被引量:4

Energy Analysis of Data Center based of Trnsys
下载PDF
导出
摘要 本文以某数据中心为模拟仿真对象,利用Trnsys软件建立了冷却系统中的冷水机组、冷却塔、冷冻泵、冷却泵、湖水泵、板式换热器等模块,对数据中心三种不同运行模式的能耗进行仿真模拟。结果表明:利用湖水进行自然冷却的数据中心能源利用效率为1.23。在采用湖水源作为自然冷源的情况下,相比于传统的机械制冷和冷却塔供冷,该数据中心的能耗分别减少了38.6%和34.7%。 This research is based on an actual data center, and Trnsys is applied to simulate chillers, cooling towers,refrigeration pumps, cooling pumps, lake pumps and plate heat exchangers. Three different operation modes of the energy consumption are simulated and analyzed. The results show that, the PUE of the lake water natural cooling system is 1.23;while using the lake water source as the cooling energy source, compare to the situations of using the traditional mechanical refrigeration system and cooling tower cooling system, the energy effectiveness of the traditional data center decreases 38.6% and 34.7% respectively.
作者 曾丽萍 雷奥军 张泉 凌丽 ZENG Li-ping;LEI Ao-jun;ZHANG Quan;LING Li(Department of Architectural Engineering,Hunan Institute of Engineering Xiangtan;College of Civil Engineering,Hunan University)
出处 《建筑热能通风空调》 2019年第11期65-68,94,共5页 Building Energy & Environment
基金 国家重点研发计划项目(2016YFE0114300) 湖南省青年联合培养基金(2015JJ6025) 湖南工程学院博士点基金
关键词 数据中心 能耗模拟 TRNSYS 能源利用效率 data center energy simulation Trnsys Power Usage Effectiveness(PUE)
  • 相关文献

参考文献1

二级参考文献3

  • 1陆耀庆.实用供热空调设计手册[M]2版.北京:中国建筑工业出版社,2008.
  • 2中国建筑设计研究院.建筑给水排水设计手册[M].2版.北京:中国建筑工业出版社,2008:567-571.
  • 3中国建筑科学研究院.公共建筑节能设计标准:GB50189-2015[S].北京:中国建筑工业出版社,2015:15-30.

共引文献13

同被引文献59

引证文献4

二级引证文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部