摘要
换流阀运行试验是确保换流阀长期稳定可靠运行的关键试验之一。在损耗补偿的基础上,基于晶闸管结温等效原则,理论推导出了不同系统频率下的运行试验等效参数的具体计算研究方法。以应用于60 Hz系统的巴西美丽山二期换流阀为例,对其在国内50 Hz的合成试验系统中进行运行试验的试验参数进行了计算,并在合成回路上进行散热器台面测温试验,对晶闸管结温进行校核,验证了运行试验等效研究方法的正确性,为后续国产换流阀走向海外提供了试验指导。
The operational test of the converter valve is one of the key tests to ensure the steady and reliable operation of the converter valve. On the basis of loss compensation,the specific calculation method of equivalent parameters of operational tests under different system frequencies is deduced based on the equivalence principle of thyristor junction temperature. Taking Belo Monte phase Ⅱ valve which is working in 60 Hz system for example,its operational test parameters in the domestic 50 Hz synthetic test system are calculated,and the temperature measuring test of the radiator table is carried out on the synthetic circuit to check the junction temperature of the thyristor. The test results prove the validity of the equivalent test method,which provides test guidance for subsequent domestic converter valve going overseas.
作者
张翔
黄华
周晨
张子敬
施洋洋
郑力
ZHANG Xiang;HUANG Hua;ZHOU Chen;ZHANG Zijing;SHI Yangyang;ZHENG Li(Nanjing NR Electric Co.,Ltd.,Nanjing 211102,China)
出处
《电力自动化设备》
EI
CSCD
北大核心
2020年第2期220-224,共5页
Electric Power Automation Equipment
关键词
换流阀
运行试验
等效研究
晶闸管结温
试验参数
converter valve
operational tests
equivalent study
thyristor junction temperature
test parameters