期刊文献+

三门核电站550 kV GIS安装要点分析及控制 被引量:1

Analysis and Control for the 550 kV GIS Installation Point of Sanmen Nuclear Power Plant
下载PDF
导出
摘要 550 kV GIS(气体绝缘金属封闭式开关设备)是利用具有优异绝缘性能的SF6气体作为绝缘和灭弧介质的组合电器。由于其结构的特殊性,对安装阶段有着严格的施工质量要求。文章通过分析GIS运行期间容易发生的绝缘类和气密性故障,针对这两大故障在三门核电站一期工程550 kV GIS的安装过程制定了相应的控制措施并严格执行,确保了GIS最终的安装质量,也为二期工程550 kV GIS的安装提供了指导及经验反馈。 550 kV GIS is the combined electrical equipment which utilizes the SF6 with high insulation capability as the insulating and arc media.Due to the special feature of the structure,its installation condition has strict quality requirement.This paper analyzes the insulation and tightness fault that occurred easily during the GIS installation,and correspondingly develops strict control measures for 550 kV installation work in Sanmen Phase Ⅰ.These measures ensure the installation quality of GIS.Meantime,it will be a reference for the 550 kV GIS installation work in Phase Ⅱ.
作者 王勋 WANG Xun(Sanmen Nuclear Power Plant Co.,Ltd.,Taizhou,Zhejiang Prow 317112,China)
出处 《中国核电》 2019年第6期646-653,共8页 China Nuclear Power
关键词 550 kV GIS 安装 要点控制 经验反馈 550kV GIS installation installation point control experience feedback
  • 相关文献

参考文献2

二级参考文献19

  • 1赖启结.两次GIS事故后的分析和思考[J].广东输电与变电技术,2005(5):55-58. 被引量:1
  • 2NING Xin,TIAN Liyan,HU Xiaoguang.Electrical Equip-ment Fault Diagnosis System Based on the Decompositon Prod-ucts of SF6[C]∥2009 IEEE International Conference on Con-trol and Automation,Christchurch.New Zealand:[s.n.],2009:9-11.
  • 3CHU F Y.SF6Decomposition in Gas-insulated Equipment[J].IEEE Trans.Electr.Insul.,1986,21(5):693-725.
  • 4TOMINAGA S,KUWAHARA H,HIROOKA K,et al.SF6Gas Analysis Technique and Its Application for Evaluation ofInternal Conditions in SF6Gas Equipment[J].IEEE Transac-tions on Power Apparatus and Systems,1981(9):4196-4206.
  • 5BECHER W,MASSONNE J.Contribution to the Decompo-sition of Sulfur Hexafluoride in Electric Arcs and Sparks[R].[S.l]:[s.n],1978.
  • 6DERDOURI A,CASANOVAS J,GROB R,et al.SparkDecomposition of SF6/H2O Mixtures[J].IEEE Transactionson Electrical Insulation,1989,24(6):1147-1157.
  • 7FREES L,SAUERS I,ELLIS H,et al.Positive Ions inSpark Breakdown of SF6[J].Journal of Physics D:AppliedPhysics,1981(14):1629-1637.
  • 8BARTAKOVA B,KRUMP J,VOSAHLIK V.The Effectof Partial Discharges upon SF6[J].Electrotechnicky Obzor.Prague,1978(67):230-241.
  • 9Van BRUNT R,HERRON J.Fundamental Processes of SF6Decomposition and Oxidation in Glow and Corona Discharges[J].IEEE Transactions on Electrical Insulation,1990,25(1):75-94.
  • 10BRUNT V R J,SIDDAGANGAPPA M.Identification ofCorona Discharge-induced SF6 Qxidation Mechanisms UsingSF6/18 O2/H126O and SF6/16 O2/H128O Gas Mixtures[J].Plas-ma Chemistry and Plasma Processing,1988,8(2):207-223.