期刊文献+

电压暂降对变频器控制回路影响及一种有效改进措施 被引量:1

The effect of voltage drop on inverter control circuit and an effective improvement measure
下载PDF
导出
摘要 在石油化工装置中,不论是工艺设备需求还是出于节能目的,变频器都在大量使用。变频器因电压暂降而造成设备停机或装置停车现象时有发生,这给企业造成很大经济损失。通过介绍电压暂降概念及其危害,结合电压暂降造成变频器停机的实例,分析变频器停机的原因--低电压。根据变频器的电压判据,提出为其直流母排增设直流电源支撑的解决方案。经改造后设备运行稳定,再未出现因电压暂降而停机的现象,是一种经济有效的解决方案,对该类工程有一定借鉴意义。 In petrochemical plants, frequency converters are widely used for both process equipment requirements and energy saving purposes. Frequency converter causes equipment shutdown or device shutdown due to voltage sag, which causes great economic losses to enterprises. By introducing the concept of voltage sag and its harmfulness, combining with the example of frequency converter shutdown caused by voltage sag, the cause of frequency converter shutdown﹣low voltage is analysed. According to the voltage criterion of frequency converter, the solution of adding DC power supply support to its DC bus is put forward. After modification, the equipment runs steadily without any. shutdown phenomenon caused by voltage sag. It is an economical and effective solution, which can be used for reference in such projects.
作者 李占勇 LI Zhan yong(Nanjing Jinling Petrochemical Engineering Co.,Ltd.,Nanjing 210042,China)
出处 《电气应用》 2020年第3期14-19,共6页 Electrotechnical Application
关键词 电压暂降 变频器 直流支撑 voltage sag frequency converter DC-BANK
  • 相关文献

参考文献3

二级参考文献6

共引文献19

同被引文献4

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部