摘要
对逆变侧交流系统因接地故障而单相跳闸后换流母线处电压的相位特征进行了研究,理论分析表明交流系统切除故障相将导致逆变器各换相电压的相位差发生变化。在此基础上,对单相跳闸后的逆变器换相过程进行了分析,发现在现有的等间隔触发方式下,直流系统的换相过程将受到影响,甚至面临换相失败的风险。因此,提出了基于触发角偏差量的换相失败判断方法,该方法能够可靠判断当前系统参数下单相跳闸是否会引发连续换相失败。基于换相电压相位差提出了一种适用于逆变侧交流系统单相跳闸后的逆变器触发方式以抑制换相失败。PSCAD仿真结果表明,所提出换相失败判断方法能可靠预测单相跳闸引发的换相失败,所提出的换流器触发方式可以有效抑制连续换相失败。
The phase characteristics of the voltage at the converter busbar after the single-phase tripping of inverter-side AC system due to the grounding fault are studied.The theoretical analysis shows that cutting the fault phase of AC system will change the phase difference of the inverter commutation voltage.On this basis,the inverter commutation process after single-phase tripping is analyzed,which shows that under the existing equal interval triggering mode,the commutation process of the DC system will be affected,and there is even the risk of commutation failure.Therefore,a commutation failure judgment method based on the amount of trigger angle deviation is proposed,which can reliably determine whether the single-phase tripping under the current system parameters will cause continuous commutation failure.Based on the phase difference of the commutation voltage,an inverter triggering method suitable for the single-phase tripping of inverter-side AC system is proposed to suppress the commutation failure.The results of PSCAD simulation show that the proposed commutation failure judging method can reliably predict the commutation failure caused by single-phase tripping,and the proposed converter triggering mode can effectively suppress the continuous commutation failure.
作者
赵盛
李博通
李斌
姚斌
ZHAO Sheng;LI Botong;LI Bin;YAO Bin(Key Laboratory of Smart Grid of Ministry of Education,School of Electrical Automation and Information Engineering,Tianjin University,Tianjin 300072,China)
出处
《电力自动化设备》
EI
CSCD
北大核心
2020年第4期17-24,55,共9页
Electric Power Automation Equipment
基金
国家电网公司总部科技项目(基于全域信息的失灵保护和自适应重合闸技术研究)。
关键词
高压直流输电
单相跳闸
触发角偏差量
换流器触发方式
连续换相失败
抑制方法
HVDC power transmission
single-phase tripping
trigger angle deviation
converter triggering mode
continuous commutation failure
suppression method