期刊文献+

AquaSee: Predict Load and Cooling System Faults of Supercomputers Using Chilled Water Data

原文传递
导出
摘要 An analysis of real-world operational data of Tianhe-1A(TH-1A)supercomputer system shows that chilled water data not only can reflect the status of a chiller system but also are related to supercomputer load.This study proposes AquaSee,a method that can predict the load and cooling system faults of supercomputers by using chilled water pressure and temperature data.This method is validated on the basis of real-world operational data of the TH-1A supercomputer system at the National Supercomputer Center in Tianjin.Datasets with various compositions are used to construct the prediction model,which is also established using different prediction sequence lengths.Experimental results show that the method that uses a combination of pressure and temperature data performs more effectively than that only consisting of either pressure or temperature data.The best inference sequence length is two points.Furthermore,an anomaly monitoring system is set up by using chilled water data to help engineers detect chiller system anomalies.
出处 《Journal of Computer Science & Technology》 SCIE EI CSCD 2020年第1期221-230,共10页 计算机科学技术学报(英文版)
基金 The work was supported by the National Key Research and Development Program Program of China under Grant No.2016YFB0201800.
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部