期刊文献+

H型钢加固混凝土板共同工作性能试验研究 被引量:3

Experimental study on common working performance of H-steel reinforced concrete slabs
原文传递
导出
摘要 为了研究后加H型钢加固混凝土板的共同工作性能,制作了12个二次成型H型钢加固混凝土板的试件,通过静力加载试验,研究了不同连接方式、植栓深度、锚栓数量(锚栓间距)及结合面的处理方式对于试件的工作性能以及破坏形态的影响。试验结果表明:通过采用植栓或穿过楼板设置螺栓连接件的方式,可使型钢梁与混凝土板具有一定的共同工作性能,形成组合梁;当采用植栓的方式进行连接时,植栓深度不小于锚栓直径的5倍,可保证锚栓不发生锚固破坏。结合面的粘贴处理方式对结合面产生滑移的荷载大小有影响,对试件的承载力没有影响;后加型钢加固混凝土板形成的组合构件并非完全意义上的组合梁,其承载力可按组合梁进行计算,但应将承载力乘以一个折减系数,建议取0.85;该组合构件的锚栓数量可参照钢结构设计规范对组合梁锚钉设置的要求进行设置,但应适当增加。 In order to study common working performance of H-steel reinforced concrete slabs, 12 post forming H-steel reinforced concrete slabs were made to carry out static loading. The influences of different connection way, plant bolts depth, the number of anchor bolts(anchor spacing) and the way of joint surface treatment were investigated. The test results show that by adopting the method of planting bolts or setting bolt connectors through the floor, the steel beam and the concrete slab can have a certain common working performance to form a composite beam. When using a plant bolt to connect, the depth of the plant bolt is not less than 5 times the diameter of the anchor bolt, which can ensure that the anchor bolt does not break. The bonding treatment method of the joint surface has an effect on the load of the slip surface, and has no influence on the bearing capacity. The composite member formed by the post-shaped steel reinforced concrete slab is not a composite beam in a complete sense, and its bearing capacity can be calculated according to the composite beam, but it should be multiplied by a coefficient. It is recommended to take 0.85. The number of anchors can refer to the setting requirements of the composite beam anchor according to standard for design of steel structures, but should be properly increased.
作者 赵考重 许洁 王永强 Zhao Kaozhong;Xu Jie;Wang Yongqiang(School of Civil Engineering,Shandong Jianzhu University,Jinan 250101,China;Engineering Research Institute of Appraisal and Strengthening,Shandong Jianzhu University,Jinan 250013,China)
出处 《建筑结构》 CSCD 北大核心 2020年第6期34-38,共5页 Building Structure
基金 国家重点研发计划项目(2017YFC0702900)。
关键词 H型钢 混凝土板 加固改造 组合梁 共同工作性能 H-beam concrete slab reinforcement and transformation composite beam common working performance
  • 相关文献

参考文献3

二级参考文献46

  • 1周凌宇,余志武,蒋丽忠.钢-混凝土组合梁界面滑移剪切变形的双重效应分析[J].工程力学,2005,22(2):104-109. 被引量:20
  • 2蒋秀根,剧锦三,傅向荣.考虑滑移效应的钢-混凝土组合梁弹性应力计算[J].工程力学,2007,24(1):143-146. 被引量:17
  • 3Roll F. The effects of differential shrinkage and creep on a composite steel concrete structure [J]. American Concrete Institute Special Publication, 1971, (8): 187-214
  • 4Johnson R P. Shrinkage induced curvature in composite beams with a cracked concrete flange [J]. Struct. Engr., 1987, 65B(4): 72-76
  • 5Bradford M A, Gilbert R I. Experiments composite beams at service loads [J]. Cir. Engng. Trans. Instn. Engrs. Austral., 1991, 33(4): 284-291
  • 6Wright H D, Witek J L, Rakib S N. Long-term creep and shrinkage in composite beams with partial connection[J]. Proc. Instn. Cir. Engrs. Structs. & Bldgs., 1992, 94(5): 187-195
  • 7Comite Euro-International Du Beton. CEB-FIP Model Code 1990 [S]. London: Thomas Telford, 1993
  • 8GBJ82--5普通混凝土长期性能和耐久性能试验方法[S].北京:中国建筑工业出版社,1997.
  • 9Eurocode 2 Design of concrete structures IS]. Part 1.1: General rules and rules for buildings. 2004
  • 10中国建筑科学研究院.混凝土收缩与徐变的试验研究[R].北京,1987.

共引文献58

同被引文献14

引证文献3

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部