摘要
针对压力无关再热型变风量末端的15种典型故障,提出了一种基于贝叶斯网络的故障诊断方法。根据某建筑实际运行系统建立了Dymola仿真模型,并基于模拟故障数据对所提出的诊断方法进行了验证。结果表明,该方法对于绝大多数故障都可以成功检测并分离,有着较高的准确性和可靠性,并且可较好地应对实际工程中存在的数据问题,将实时故障诊断的应用场景进一步推广。
Aiming at 15typical faults of the pressure independent variable air volume(VAV)terminal with reheat coil,proposes a Bayesian network-based fault diagnosis method(FDD).Establishes a Dymola simulation model based on an actual VAV system,and verifies the performance of the proposed method based on simulated fault data.The results show that this method performs well at:(1)detecting and isolating most faults with high accuracy and reliability,(2)dealing with the data problems existing in actual engineering,(3)further popularizing the application of real-time fault diagnosis.
作者
李以通
李铮伟
杨光
周立宁
付强
贾晓晴
丁宏研
Li Yitong;Li Zhengwei;Yang Guang;Zhou Lining;Fu Qiang;Jia Xiaoqing;Ding Hongyan(China Academy of Building Research,Beijing,China)
出处
《暖通空调》
2020年第4期21-27,共7页
Heating Ventilating & Air Conditioning
基金
“十三五”国家重点研发计划“绿色建筑及建筑工业化”专项“既有公共建筑综合性能提升与改造关键技术”(编号:2016YFC0700700)。
关键词
故障诊断
贝叶斯网络
压力无关再热型变风量末端
诊断准确度
检测准确度
fault diagnosis
Bayesian network
pressure independent VAV terminal with reheat coil
diagnostic accuracy
detection accuracy