摘要
对1000kV特高压南阳站110kV并联电容器补偿装置管母支撑绝缘子进行了受力及风荷载仿真分析,得出在支撑绝缘子等部件结构完好的条件下,在正常运行过程中,绝缘子不会发生破坏,仅当端部受到大于400 kg以上的集中载荷作用时,绝缘子才可能发生破坏的结论。为特高压工程的建设提供参考。
This paper analyzed the force and wind load simulation of 110 kV shunt capacitor compensation device tube post insulator at 1000 kV UHV Nanyang Station.The conclusion is that if the components of the post insulator are in good condition,insulators will not be damaged during the normal operation;and only when the ends are subjected to concentrated loads greater than 400 kg,the insulators will be destroyed.Provide reference for the construction of UHV project.
作者
李茹勤
乔振朋
郭果
刘涛
LI Ruqin;QIAO Zhenpeng;GUO Guo;LIU Tao(State Grid Henan Electric Power Corporation Maintenance Company,Zhengzhou 450007,China)
出处
《电瓷避雷器》
CAS
北大核心
2020年第2期256-260,共5页
Insulators and Surge Arresters