R22制冷系统改造成R22/CO 2载冷系统的可行性分析 被引量:2

Feasibility analysis of R22 refrigeration system reconstructed to R22/CO 2 secondary refrigeration system
下载PDF
导出
摘要 基于一个实际工程案例,在不更换压缩机组和冷凝器的前提下,将原R22制冷系统改造成R22/CO 2载冷系统,机房外管道用量减少60.3%,R22制冷剂的充注量减少68.5%,系统能效比下降9.6%,总成本增加4.9%。分析结果可以为R22制冷系统的改造提供新的思路。 Based on a real project,a R22 refrigeration system is reconstructed to a R22/CO 2 secondary refrigeration system without changing its compressor unit and condenser.The amount of pipe outside computer room is reduced by 60.3%,the charging amount of R22 is reduced by 68.5%,EER of system is decreased by 9.6%,and the total cost is increased by 4.9%.The analysis results will provide a new approach for the reconstruction of R22 refrigeration system.
作者 元爱民 Yuan Aimin(Panasonic Appliance Refrigeration System(Dalian)Co.,Ltd.)
出处 《制冷与空调》 2020年第4期59-63,共5页 Refrigeration and Air-Conditioning
关键词 制冷系统 CO 2 R22 载冷系统 refrigeration system CO 2 R22 secondary refrigeration system
  • 相关文献

参考文献5

二级参考文献33

  • 1张术学.CO_2/NH_3复叠制冷浅析[J].制冷与空调,2006,6(1):59-62. 被引量:9
  • 2李郁,张永桂,李文江.大型氨制冷系统电子膨胀阀的推广与应用[J].冷藏技术,2006(3):19-20. 被引量:3
  • 3杨一凡.氨制冷技术的应用现状及发展趋势[J].制冷学报,2007,28(4):12-19. 被引量:64
  • 4Kuniaki Kawamura, S Akaboshi, Akito Machida. De sign considerations for an NH: System Utilizing CO2 as a Secondary Refrigerant in Tokyo [C]//2008 lIAR Ammonia Refrigeration Conference g: Exhibition. 2008.
  • 5Handschuh. Design criteria for CO2 evaporators[C]// GTZ Proklima. Eschborn, Germany, 2008.
  • 6Kawamura, Akaboshi, Machida, et al. Ammonia refrig-erationsystem with C02 as a secondary refrigerant[C]// IIAR proceedings. USA,2007.
  • 7MikhaiIov, Matthiesen. Comparative analysis of sec ondary CO2 systems and water based brines in indus- trial and commercial refrigeration applications [C]// IIR GL Conference. Copenhagen, Denmark, 2010.
  • 8David Hinde, Shitong Zha, Lin Lan. Carbon Dioxide In North American Supermarkets [J]. ASHRAE Jour- nal,2009,51(2) :18 26.
  • 9Danfoss. C02 refrigerant for Industrial Refrigeration [G/OL] Industrial Refrigeration, http://www, dan- loss. com/BusinessAreas/RefrigerationAnd AirCondi tioning/Industries/Industrial Refrigeration. htm.
  • 10Danfoss. The use of AKV (A) electronic injection valves for air coolers in pumped (flooded) CO2 sys- tems[G/OL]. Industrial Refrigeration, http ://www. danfoss, com/BusinessAreas/RefrigerationAnd Air- Conditioning/Industries/Industrial Refrigeration. htm.

共引文献25

同被引文献55

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部