不同流程布置风冷式冷凝器的数值研究 被引量:3

Numerical Study on Air-cooled Condenser with Different Circuit Arrangements
下载PDF
导出
摘要 为了节省实验资源并缩短实验周期,本文应用三维分布参数模型对风冷式冷凝器的4种流程布置和5组不同制冷剂流量工况的流动换热性能进行数值研究,并通过实验验证了模型的可靠性。仿真模型对制冷剂换热量的预测与相同工况下的实验值的相对误差在±10%以内;制冷剂压降的预测值相对误差在±15%以内。模拟结果表明:为了使换热量尽量大的同时熵产数小,流程布置合流次数为0、2、3时所对应的最佳质量流量范围分别为511~540 kg/h、472~511 kg/h和432~472 kg/h。研究发现在低质量流量区域,选择有合流的管路更具优势;在高质量流量区域,则选择无合流的管路具有更好的传热特性。 To save experimental resources and shorten the experimental cycle,a three-dimensional distributed parameter model was used to study the heat transfer performance of air-cooled condensers.Four kinds of circuit arrangements and five groups under different refrigerant flow conditions were compared,and the reliability of the model was experimentally verified.The relative error of the simulation model for predicting the heat transfer of refrigerants was less than±10%,compared with the experimental values under the same working conditions,and the relative error of the predicted value of refrigerant pressure drop was less than±15%.Simulations demonstrated that the optimal mass flow rate ranges corresponding to the confluences number of the circuit arrangements of 0,2,and 3 were 511~540kg/h,472~511kg/h,and 432~472kg/h,respectively,reflecting ahigh heat transfer and low entropy production.The pipeline with confluence exhibited more advantages in the low mass flow rate area,while the non-confluence pipeline exhibited better heat transfer characteristics in the high mass flow rate area.
作者 李晓静 臧润清 张晨旭 Li Xiaojing;Zang Runqing;Zhang Chenxun(School of Mechanical Engineering, Tianjin University of Commerce, Tianjin, 300134, China)
出处 《制冷学报》 CAS CSCD 北大核心 2020年第3期51-57,共7页 Journal of Refrigeration
关键词 风冷式冷凝器 流动换热 流程布置 数值研究 air-cooled condenser circuit arrangement flow and heat transfer numerical study
  • 相关文献

参考文献4

二级参考文献39

  • 1张祉佑.制冷原理与设备[M].北京:机械工业出版社,1986..
  • 2Oskarsson S P, Krakow K I, Lin S. Evaporator models for operation with dry, wet, and frosted finned surfaces, part I: Heat transfer and fluid flow theory [J]. ASHRAE Transactions, 1990, Vol.96: 373-380.
  • 3Green H, Roberts L. The effect of aircoil design on the performance of heat pumps and air conditioners [J].ASHRAE Transations, 1996, Vol. 102: 257-265.
  • 4Jolly P G, et al. Simulation and measurement on the fullload performance of a refrigeration system in a shipping container[J]. Int. J. of Refrig,2000, Vol. 23: 112-126.
  • 5Oskarsson S P,et al. Evaporator models for operation with dry, wet, and frosted finned surfaces, part Ⅱ: Evaporator models and verification[J]. ASHRAE Transaction, 1990,Vol.96: 381-392.
  • 6Martins Costa M L, Parise J A. A three-zone simulation model for air-cooled condensers[J]. Heat Recovery Systems & CHP, 1993, Vol. 13: 97-113.
  • 7Domanski P A. Simulation of an evaporator with nonuniform one-dimensional air distribution[J]. ASHRAE Trans,1991, Vol. 97: 793-802.
  • 8Jia X, et al. A distributed model for prediction of the transient response of an evaporator [J]. Int. J. of Refrig,1995, Vol. 18: 336-342.
  • 9John Judge, Reinhard Radermacher. A heat exchanger model for mixtures and pure refrigerant cycle simulations[J] .Int. J.of Refrig,1997, Vol.20: 244-255.
  • 10Bensafi A, et al. CYRANO: A computational model for the detailed design of palte -fin-and-tube heat exchangers using pure and mixed refrigerants[J]. Int. J. of Refrig,1997, Vol.20: 218-228.

共引文献29

同被引文献17

引证文献3

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部