摘要 通过搭建重力循环柜试验平台,测试重力循环柜在梅雨季节下的供冷除湿情况。选择江苏昆山作为高湿地区代表,研究供水温度、供水流量等变量对重力循环柜运行性能的影响,并探究供水温度和供水流量对毛细管壁温升、室内温湿度、室内人体热舒适和室内环境响应速度的影响。结果表明:在梅雨季节,重力循环柜的供冷除湿性能稳定良好,供冷量为1200~1800 W,除湿量为0.5~1.0kg/h;室内温度为23~24℃,相对湿度为50%~65%;室内环境响应速度较快,当改变房间的设定温、湿度时,调节供水温度比调节供水流量更有效。 The cooling and dehumidification performance of gravity circulation cabinet on rainy season was established and tested.The Kunshan district was selected as representative high-humidity area.The influence of water temperature and water flow rate on gravity circulation cabinet performance were tested,and the changes of capillary temperature,indoor temperature and humidity,human thermal comfort,environmental response were explored.The experimental results show that the gravity circulation cabinet has stable cooling and dehumidification performance on rainy season,the cooling capacity of gravity circulation cabinet is 12001800 W,the dehumidification capacity is 0.51.0 kg/h;the indoor temperature is 2324℃and the relative humidity is 50%65%.The indoor environment is more responsive,adjusting the circulating water temperature is more effective than circulating water flow when changing the indoor temperature and humidity.
作者 葛玉箫 梁珍 于英娜 GE Yuxiao;LIANG Zhen;YU Yingna(College of Environmental Science and Engineering,Donghua University,Shanghai 201620,China;Kunshan KST Co.Ltd.,Suzhou 215300,China)
出处 《东华大学学报(自然科学版)》 CAS 北大核心 2020年第3期457-462,478,共7页 Journal of Donghua University(Natural Science)
关键词 毛细管 重力循环柜 供冷除湿 实测研究 capillary gravity circulation cabinet cooling and dehumidification experimental study
  • 相关文献

参考文献7

二级参考文献34

  • 1[美]S V帕坦卡 郭宽良(译).传热和流体流动的数值方法[M].北京科学技术出版社,1984..
  • 2阚久峰.送风房间三维紊流流动及传热的数值计算.哈尔滨建筑工程学院硕士论文[M].,1989..
  • 3李翠敏 方修睦 赵加宁 等.毛细管重力循环供热装置的设计及热工性能的实验研究.暖通空调,2008,38:21-25.
  • 4Jae-Weon Jeong. Energy conservation benefits of a ded- icated outdoor air system with Parallel sensible cooling by ceiling radiant Panels [ C ]. ASHRAE Transactions, 2003,102( 1 ) :627-637.
  • 5Rt WRoth, Etlef WestPhalen, Ohn Dieekman, et al. Energy consumption characteristics building HVAC systems, volumel 11 : Energy Savings Potential [ M ]. 2002.
  • 6薛殿华.空气调节[M].北京:北京清华大学出版社,1999.
  • 7EN14240. Ventilation for buildings-Chilled ceilings- Testing and rating[ S]. European Standard Norme Eu- ropeenne Enropaische Norm.
  • 8ASHRAE. ANSI/ASHRAE Standard 55-2004 Thermal environmental conditions for human occupancy[ S]. At- lanta: American Society of Heating, Refrigerating and Air-conditioning Engineers Inc, 2004.
  • 9POFanger. Thermal comfort: Analysis and application in environmental engineering [ M ]. Danish Technical Press Copenhagen, 1970:58.
  • 102001-Fundamentals. 1708 Thermal Comfort [ M ]. ASHRAE Handbook, 2001-2003 : 133.

共引文献49

同被引文献18

引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部