呼吸科诊室内微生物污染物分布特性的数值模拟 被引量:3

Numerical Simulation of Microbial Pollutants in Respiratory Clinic
下载PDF
导出
摘要 通过数值模拟方法,针对采用侧送下回通风方式的呼吸科诊室,研究分析其在不同季节工况下,患者说话所产生的微生物污染物的运动分布特性。结果发现:冬、夏季工况中诊室内微生物污染物的空间分布有较大差异。污染物与夏季送风气温差较大,在浮升力作用下可运动到诊室高处,而冬季的送风气流由于自身温度较高,漂浮在诊室上部空间,使污染物聚集在送风气流以下高度,导致就诊区域及呼吸高度水平面上的微生物污染物浓度冬季高于夏季。 The numerical simulation analysis on the dispersion and distribution of microbial pollutants generated by patient’ s speech in the respiratory clinic with side-supply and low-return system in different seasons was present. The results show that the spatial distribution of microbial contaminants in the consultation room was different in winter and summer conditions. Under the action of buoyancy, the pollutants can move to the upper part of the consulting room, while the air supply in winter due to its higher temperature, floating in the upper space of the consulting room, and make the pollutants gathered at the height below the airflow, which leads to the concentration of microbial contaminants in the area of the visit and the level of breathing height is higher in winter than in summer.
作者 李梦雪 刘刚 赵红霞 解紫茹 LI Meng-xue;LIU Gang;ZHAO Hong-xia;XIE Zi-ru(School of Environmental Science and Engineering,Donghua University)
出处 《建筑热能通风空调》 2020年第5期44-48,10,共6页 Building Energy & Environment
关键词 微生物污染物 诊室 分布特征 CFD microbial pollutants consultation room distribution characteristics CFD
  • 相关文献

参考文献3

二级参考文献47

  • 1胡庆轩,徐秀芝,童咏仪,车凤翔,蔡增林,鲁志新,温青莉,何亦祥.沈阳市大气微生物的研究Ⅳ.大气真菌粒数中值直径及粒度分布[J].微生物学通报,1994,21(6):353-356. 被引量:18
  • 2张波,孟紫强.大气生物污染与健康的研究[J].城市环境与城市生态,1995,8(4):15-18. 被引量:9
  • 3郭丽萍,王保法,马俊义,刘树卿,孙以瑜.危重院内下呼吸道感染的病原学及细菌耐药性研究[J].中国急救医学,1997,17(2):23-25. 被引量:6
  • 4Ryan K J. Sherris medical microbiology[M]. 3rd ed. East Norwalk: Appleton & Lange,1994..401-416.
  • 5Mandell G L. Principles and practice of infectious disea- ses[M]. New York.. Wiley,1985 : 213-242.
  • 6Zhao B, Li X, Yan Q. A simplified system for indoor airflow simulation. Building and Environment, 2003,38(4): 543- 552.
  • 7Chen, Q, Xu W. A zero-equation turbulence model for indoor air flow simulation. Energy and Buildings, 1998,28(2): 137-144.
  • 8Zhao B, Lu J, Li X. Numerical simulation of air distribution in chair ventilated room by simplified methodology. In: ASHRAE Trans, 2002,108: 1079- 1083.
  • 9Holmberg S, Li Y. Modeling of the indoor environment-particle dispersion and deposition. Indoor air, 1998, 8: 113-122.
  • 10Murakami S, Kato S, Nagano, et al. Diffusion characteristics of airborne particles with gravitational settling in a convection-dominant indoor flow field. In: ASHRAE Trans, 1992,98(1):82-97.

共引文献44

同被引文献20

引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部