期刊文献+

直接接触式烟气冷凝余热回收装置性能实验研究 被引量:7

Experimental study on performance of a direct contact flue gas condensing waste heat recovery device
下载PDF
导出
摘要 提出一种直接接触式烟气冷凝余热回收装置,该装置将低温喷淋水溶液与高温烟气进行逆流换热,回收燃气锅炉烟气的冷凝余热。以燃气壁挂炉作为烟气发生源搭建了实验台,研究了喷淋水温度、液气比、喷淋高度对该装置余热回收性能的影响。结果显示:当喷淋水温度为20℃、液气比为13、喷淋高度为1.26 m时,该装置能将排烟温度从102℃降至33℃,余热回收效率可达14%。 Proposes a direct contact flue gas condensing waste heat recovery device,which carries out countercurrent heat transfer between low-temperature spray aqueous solution and high-temperature flue gas to recover condensing waste heat from the flue gas of gas-fired boiler.Sets up an experimental bench using a wall-mounted gas-fired boiler as a flue gas source.Studies the influences of spray water temperature,liquid-gas ratio and spray height on the waste heat recovery performance of the device.The results show that when the spray water temperature is 20℃,the liquid-gas ratio is 13,and the spray height is 1.26 m,the device can decrease the smoke exhaust temperature from 102℃to 33℃,with the waste heat recovery efficiency up to 14%.
作者 张群力 张晓月 曹明凯 Zhang Qunli;Zhang Xiaoyue;Cao Mingkai(Beijing University of Civil Engineering and Architecture,Beijing,China;不详)
出处 《暖通空调》 2020年第6期124-128,共5页 Heating Ventilating & Air Conditioning
基金 北京市自然科学基金重点项目(编号:SQKZ201510016001) “十三五”国家重点研发计划专项(编号:2017YFC0702200)。
关键词 燃气锅炉 冷凝余热回收 直接接触式换热 喷淋水温度 液气比 喷淋高度 节能 gas-fired boiler condensing waste heat recovery direct contact heat transfer spray water temperature liquid-gas ratio spray height energy saving
  • 相关文献

参考文献4

二级参考文献18

共引文献37

同被引文献73

引证文献7

二级引证文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部