摘要
某10 kV油机系统在现场带载试验过程中,当加载超过额定容量的50%时,出现电压持续波动.通过故障树分析发现,根本原因是非线性负载产生的谐波电流.采取重新整定AVR参数、加装滤波装置的措施,解决了该问题.
During the on-site load test of a 10 kV oil engine system,when the load exceeds 50%of the rated capacity,the voltage fl uctuates continuously.Through fault tree analysis,it is found that the root cause is harmonic current generated by nonlinear load.The problem was solved by readjusting AVR parameters and installing fi lter.
作者
赵铁山
陈彦虎
向祝强
易哲飞
阳衡东
Zhao Tie-shan;Chen Yan-hu;Xiang Zhu-qiang;Yi Zhe-fei;Yang Heng-dong
出处
《电力系统装备》
2020年第10期143-144,共2页
Electric Power System Equipment
关键词
10kV油机系统
非线性负载
电压波动
整定参数
滤波
10 kV oil engine system
nonlinear load
voltage fl uctuation
setting parameters
fi ltering