一起主变压器高压套管介质损耗异常及处理 被引量:2

Abnormal Dielectric Loss of High Voltage Bushing in Main Transformer and Its Treatment
下载PDF
导出
摘要 变压器高压套管介质损耗数据异常是现阶段电力系统当中常见的变压器故障现象之一,通过测试高压套管介质损耗可以有效地发现绝缘老化、受潮、开裂等不良状态。本文通过介绍某水力发电厂1号主变压器停电预防性试验时,发现其高压套管介质损耗增大超标的情况,采取通过发电机带主变压器零起升压的方法,解决这一问题,并结合相关资料给出超标的原因,并提出预防措施。 Abnormal dielectric loss data of high voltage bushing of transformer is one of the common transformer fault phenomena in the current power system.By testing the dielectric loss of high voltage bushing,it can effectively find out the bad state of insulation aging,moisture,cracking and so on.This paper introduces the situation that the dielectric loss of the high-voltage bushing increases beyond the standard during the pre test of the No.1 main transformer outage in a hydropower plant,and adopts the method of boosting the voltage from zero of the generator with the main transformer to solve this problem.Combined with the relevant data,the causes of the exceeding standard are given,and the preventive measures are put forward.
作者 穆强 喻勇丽 李奇艳 MU Qiang;YU Yongli;LI Qiyan(Hunan Willing Electric Power Engineering Co.,Ltd,Changsha 410000,China)
出处 《水电与抽水蓄能》 2020年第3期88-90,106,共4页 Hydropower and Pumped Storage
关键词 主变压器 高压套管 环氧树脂浸纸 介质损耗 极化 main transformer high voltage bushing epoxy resin impregnated paper dielectric loss polarization