期刊文献+

基于频域介电谱分析的热老化油浸式套管受潮特性研究 被引量:5

Study on Characteristics of Oil-immersed Bushings with Thermally Aged and Dampened Insulation Based on Frequency Domain Dielectric Spectrum Analysis
下载PDF
导出
摘要 油浸式套管绝缘性能下降是引发套管故障的重要原因。为了研究绝缘受潮及老化程度对油浸式套管绝缘性能的影响,基于油浸式套管的实际绝缘结构,设计并制作了套管电容芯子的实体缩比模型,并对其进行加速热老化和受潮处理,最后对不同老化程度的样品进行频域介电谱测量和分析。研究结果为频域介电谱法应用于油浸式套管老化状态评估提供了参考。 The decrease in insulation performance of oil-immersed bushings is an important cause of bushing faults.In order to study the influence of insulation moisture and aging on the insulation performance of oil-immersed bushings,physically scaled models of the bushing capacitor core were designed and produced based on the actual insulation structure of oil-immersed bushings,and accelerated thermal aging and moisture treatment were performed.Finally,frequency domain dielectric spectra of samples with different aging levels were measured and analyzed.The research results provide a reference point for the application of frequency domain dielectric spectra to the aging status evaluation of oil-immersed bushings.
作者 颜海俊 黎大健 张磊 陈梁远 YAN Haijun;LI Dajian;ZHANG Lei;CHEN Liangyuan(Electric Power Research Institute of Guangxi Power Grid Co.,Ltd.,Guangxi Nanning 530023,China)
出处 《广西电力》 2020年第3期8-15,共8页 Guangxi Electric Power
基金 广西电网有限责任公司科技项目(GXKJXM20180355)。
关键词 油纸绝缘 复介电常数 界面极化 电容芯子 oil-paper insulation complex dielectric constant interface polarization capacitor core
  • 相关文献

参考文献4

二级参考文献61

  • 1田杰,段绍辉,许昊,汤明杰,张冠军.温度及老化状态对油纸绝缘时域介电响应特性影响的实验研究[J].中国电机工程学报,2012,32(S1):69-75. 被引量:26
  • 2杨丽君,廖瑞金,孙才新,李剑,梁帅伟.油纸绝缘老化阶段的多元统计分析[J].中国电机工程学报,2005,25(18):151-156. 被引量:34
  • 3赵双孔.介电谱方法及应用[M].北京:化学工业出版社,2008.
  • 4科埃略 R.电介质材料及其介电性能[M].北京:科学出版社,2000.
  • 5Lundgaard L E, Hansen W. Linhjell D,et al. Aging ofoil-impregnated paper in power transformers [J]. IEEETransactions on Power Delivery* 2004,19(1): 230-239.
  • 6Oommen T V . Moisture equilibrium charts for transformerinsulation dying practice [J]. IEEE Transactions on PowerApparatus System,1984,103(10): 3063-3067.
  • 7Emsley AM, Xiao X, Hey wood R J, et al. Degradationof cellulosic insulation in power transformers. Part 3:effects of oxygen and water in ageing in oil[J]. IEEProceedings-Science, Measurement and Technology,2000, 147(3): 115-119.
  • 8Du Y,Zahn M, Lesieutre B C,et al. Moisture equilibriumin transformer paper-oil systems[J]. Electrical InsulationMagazine, 1999,15(1): 11-20.
  • 9Zaengl W S . Dielectric spectroscopy in time andfrequency domain for HV power equipment I. Theoreticalconsiderations[J]. Electrical Insulation Magazine, IEEE,2003,19(5): 5-19.
  • 10Ekanayake C. Diagnosis of moisture in transformerinsulation application of frequency domain spectroscopy[D]. Sweden: Chalmers University of Technology, 2006.